K-O2 Oxygen Sensor 

5/20/2022 

Kele, Inc. • 3300 Brother Blvd. • Memphis, TN  38133 

Page 6 

 

www.kele.com

 

 

Status LED Color  Operational Status 

Description 

 

Concentration is above 

the warning/ventilation 

threshold.  

No relay 

outputs are active.

 

 

Concentration is below 

the warning/ventilation 

threshold and above the 

alarm threshold.  

Warning/ventilation relay 

is active.

 

 

Concentration is below 

the alarm threshold.  

Both 

warning/ventilation and 

alarm relays are active

 

End of Life warning.  

Sensor has reached the 

end of its rated service life 

and should be replaced.  

Relays and analog 

outputs continue to 

function normally.

 

 

Sensor Expired. 

Warning/ventilation relay 

is active and analog 

output is 4 mA.

 

(refer to Section 7) 

Table 7:

 Front Panel Status LED Indications 

During Normal Operation. 

O

PERATIONAL 

D

ESCRIPTION

 

The K-O2 is a two-stage ventilation and alarm controller that senses the oxygen concentration in the ambient 
space around it and operates a Warning/Ventilation contact closure that can be used to operate ventilation fans 
when reduced levels of oxygen are detected.  If the oxygen concentration approaches unsafe levels, a second 
contact closure is operated; typically to trigger an alarm.   

The gas sensor is a calibrated module that can be replaced with minimal effort when it reaches end-of-life (EOL), 
while leaving the main control mounted and wired (refer to 

Section 7.1

). 

The front cover has an LED status indicator that illuminates in different colors to indicate normal (green), 
Warning/Ventilation (yellow), and Alarm (red) conditions.  Blinking red indicates that the sensor is NOT 
operational.  While the LED is blinking red, the analog output is delivering 4 mA to indicate the error. 

The concentration of oxygen in the ambient air is reported at the controller’s analog current-loop output as 
percent by volume.  The analog output ranges from 4 to 20mA (refer to Table 4 and Table 5). 

 

 

 

 

 

 

 

 

 

 

4.1  S

PECIAL 

M

ODES

 

The K-O2 operates in several modes as shown in 

Table 

9

.Table

 9

:  K-O2 Operating Modes

 

Normal operation is as described above.  During standby 
mode the sensor is stabilizing and analog output is held at 20 
mA.   

During span calibration the sensor’s sensitivity is compared 
to its sensitivity at initial factory calibration.  If its sensitivity 
has fallen below manufacturer’s specification the K-O2 goes 
into Sensor Expired mode with the analog output held at 4 
mA and only the Warning/Ventilation relay activated. 

 

Figure 7

:  

Front Cover Status Led

 

Содержание K-O2

Страница 1: ...mphis TN 38133 Revision 5 20 2022 www kele com 90 0007 00A K O2 xx Oxygen Sensor Transmitter and Two Stage Alarm Controller User s Manual K O2 H5 5 year sensor K O2 H10 10 year sensor K O2 S5 5 year s...

Страница 2: ...ional Description 5 4 1 Special Modes 6 4 2 Warning Ventilation and Alarm Conditions 7 4 3 Setting Ventilation and Alarm Thresholds 7 4 4 Concentration Reporting 7 5 Sensor Calibration 7 5 1 Calibrati...

Страница 3: ...sor life K O2 H5 Lockable hinged enclosure with 10 year sensor life K O2 H10 Table 1 K O2 family Part numbers All K O2 xx models are shipped with either 5 year life K O2 x5 or 10 year life K O2 x10 fa...

Страница 4: ...ply separate transformer not required Power Consumption 5W Control Relays 2 separate SPDT line voltage capable relays for warning ventilation and alarm outputs UL rated 10 Amps max at 120 277 VAC or 3...

Страница 5: ...water entry DO NOT USE THE VENT HOLES FOR WIRE ENTRY 1 This unit is designed to mount to a rigid vibration free surface near the middle of the area to be monitored about 5 feet above the floor 2 It s...

Страница 6: ...of the terminal and returns to the terminal The oxygen sensor output is provided at the terminal highlighted in Figure 3 Analog output connection has polarity as labeled on the controller silkscreen...

Страница 7: ...to the COM location of screw terminal 5 Plug the relay output screw terminal back into the correct location on controller board 3 3 POWER CONNECTION The K O2 has a fully isolated unpolarized power inp...

Страница 8: ...a second contact closure is operated typically to trigger an alarm The gas sensor is a calibrated module that can be replaced with minimal effort when it reaches end of life EOL while leaving the main...

Страница 9: ...ormation When the concentration of oxygen falls below its configured warning ventilation threshold the WARNING VENTILATION relay output is activated When the concentration falls below the alarm thresh...

Страница 10: ...adequate and requires no calibration gas All that s required is the certainty of fresh air around the sensor For accuracy at lower oxygen percentages a zero calibration before the span calibration is...

Страница 11: ...rictor fitted to the narrow end of the cal cap at a pressure of 10 psi 5 2 CALIBRATION GAS CONNECTION A schematic of the calibration gas tubing connection between the regulator and the calibration cap...

Страница 12: ...tion gas has been removed the calibration has been applied and the unit is in standby for two minutes while the sensor re equilibrates to the ambient atmosphere before normal operation resumes The cal...

Страница 13: ...turns to steady GREEN OR 3B If NOT successful blinking RED The most likely causes of span gas sampling failure are Insufficient gas flow or leaks around the calibration adapter not completely immersin...

Страница 14: ...n in To replace a sensor module with a new factory calibrated one follow the steps below 1 Open the controller s front cover 2 Unplug the controllers power connector refer to Figure 6 3 Unplug the sen...

Страница 15: ...patible with those Products Unless KELE agrees otherwise to obtain service under this warranty Buyer must pack any nonconforming Product carefully and ship it postpaid or freight prepaid to Kele Inc a...

Страница 16: ...tect common failures If a failure is detected the front cover status LED will blink slowly RED the warning relay will be activated and the concentration reporting analog output will stay at 4 mA until...

Отзывы: