Electrical installation
4.7 Operation on different mains systems
Before you use systems other than TN or TT, please contact us. Your sales
representative or application engineer at KEBA will be pleased to provide you with
information on the boundary conditions that are to be met (e.g. compliance with the
EMC Directive, effects on CE and the safety functions, etc.)
CAUTION!
Damage to the device due to incorrect operation!
Carelessness may result in significant damage.
Pay attention to all conditions stipulated for the operation of the devices on different mains
systems.
4.7.1
Operation of the ServoOne CM-P on
TN and TT
system
:
Operation is only allowed:
y
With phase voltages 3 x 230 V, 3 x 400 V and 3 x 480 V
y
If the star point of the supply system is earthed and
y
The supply system conforms to maximum overvoltage category III as per
EN 61800-5-1 at a system voltage (phase conductor
→
star point) of maximum
277 V.
Operation is not allowed:
y
For supply with 1 x 230 V or higher single-phase mains voltages
NOTE:
For ordering information on connector sets, see system catalogue
"Automation System SystemOne“ (ID no. 1400.205B.x-xx).
NOTE:
The operating regulations in the place of use as well as national and regional
regulations for cable protection are to be followed!
The time between the two switch-on processes for the mains voltage must be
at least 2 minutes.
4.6.3
Residual current device
If local regulations require the installation of a residual current device, the following
applies:
NOTE:
In case of a fault the axis controller in the axis group is able to generate DC
fault currents without zero crossing. The multi-axis system must therefore only
be operated with type B residual current device (RCDs) for AC fault currents,
pulsating or smooth DC fault currents that are suitable for drive controller
operation, see IEC 60755.
Residual current monitoring devices (RCMs) suitable for drive controllers can also be
used for monitoring purposes.
4.6.4
Fuses
For compliance with device safety as per EN61800-5-1, use mains fuses of utilisation
class gG that disconnect the device from the mains in the event of a fault.
Terminal
Device
Fuse
X8/L1, L2, L3
SOCM-P.0004, SOCM-P.0010 (BG1)
3 x 35 A (gG)
X8/L1, L2, L3
SOCM-P.0022 (BG2)
3 x 63 A (gG)
See also connection example in Chapter 4.15.1
Table 4.6
Mains fuses, ServoOne CM-P supply unit