Operation Manual Supply Unit SO CM-P BG1+2
ID no.: 1400.201B.5-00 Date: 02/2020
CAUTION!
DAMAGE TO THE DEVICE DUE TO OVERLOAD IN THE DC LINK!
x
Carelessness may result in significant damage.
The maximum overall capacitance of the multi-axis system DC link must not exceed the value
stated.
NOTE
:
In the overall axis group, a DC link capacitance of ≥ 100 µF/kW (for 3 x 400 V)
or ≥ 170 µF/kW (for 3 x 230 V), referred to the highest rated power that
occurs, must be provided. This capacitance is determined by adding together
the capacitances of the individual devices. The root mean square of the active
power for a load cycle is defined as the active power.
A.1.1
Technical data, brake chopper BG1
Device
Unit
SOCM-P.0010 / SOCM-P.0110
Mains voltage
V AC
230
400
480
Brake chopper power electronics
Brake chopper switching threshold
V
411
652
765
Overvoltage protection
V
446
687
800
Continuous braking power [kW]
kW
1.8
3
3
Peak braking power for maximum 0.5 s *)
kW
8
13
16
Maximum ohmic resistance of an externally
installed braking resistor
Ω
60
90
90
Minimum ohmic resistance of an externally
installed braking resistor
Ω
21
33
38
Supply unit with integrated braking resistor: (model SO CM-P.xxxx.1
1
xx.x)
Continuous braking power
W
75
Peak braking power for maximum 0.5 s *)
kW
3
Ohmic resistance of the integrated braking resistor
Ω
56
*) After this time shutdown is initiated based on I
2
x t
Table A.2
Brake chopper BG1
A
Appendix
A.1 Technical data, supply unit BG1
Device
Unit
SOCM-P.0010 / SOCM-P.0110
Input, mains side
Mains voltage U
N
± 10 %, 3 times
V AC
230
400
480
Continuous current [A
AC eff
], typical
A
eff
23
23
19
Peak current [A
AC
], typical
A
eff
46
46
38
Continuous power, typical (depending on mains
impedance)
kVA
9
16
Rectifier power dissipation, typical
W
50
Asymmetry of the mains voltage
±3 % max.
Frequency
50-60 Hz ± 10%
Max. cable cross-section X12
1.5 ... 6 mm
2
(fine-stranded cable with/without ferrules) mm
2
DC link output
DC link voltage typical *
V DC
325
565
678
Continuous current
A DC
18
18
15
Peak current 2 x I
N
for 1 s mains choke not required
A DC
36
36
30
Continuous power P
N
kW
5.8
10
10
Peak power 2 x P
N
for 1 s
kW
11.6
20
20
DC link capacitance only CM-P
µF
330
Required total DC link capacitance for continuous
power
µF
1000
Max. permissible DC link capacitance SO CM + SO
CM-P
µF
2000 (1670 + 330) max.
Power dissipation P
rated
in the interior
W
85
* Load-dependent
Table A.1
Technical data, ServoOne CM-P BG1