Operation Manual Supply Unit SO CM-P BG1+2
ID no.: 1400.201B.5-00 Date: 02/2020
A.8 Mains choke
We recommend the usage of mains chokes to reduce the peak system currents and
therefore also the distortion (THD) in the system and to prolong the life of the axis
controller (for use on the ServoOne CM-P supply unit BG1+2).
NOTE:
For these devices, it is also to be ensured that the mains choke is installed on
the mains side in front of the mains filter.
Use the following mains chokes for the ServoOne CM-P supply unit BG1+2
Device
Related mains choke
SO CM-P.0x10
LR34.20-UR
SO CM-P.0x22
LR34.44-UR
Table E.12
Total leakage capacitances on mains filters
NOTE:
If the rated power of the ServoOne CM-P supply unit BG1+2 is not utilised,
smaller mains chokes to match the related mains input current can be used.