Depth:
75 mm
Weight:
ca. 250 g (without cablel)
Drop-tested:
1.5 m on industrial floor
12.5 E-Stop ratings (respective grey halt-button)
Rated voltage:
24 V DC
Minimum current:
10 mA (each contact)
Maximum current:
1000 mA (each contact)
Utilization category:
DC-13 (in accordance with IEC 60947-5-1)
Schlegel:
B
10d
: 250 000
Design:
2 circuits, external wiring
Galvanic isolation:
500 V AC to the rest
12.6 Enabling control device
Output type:
Solid-state output
Voltage:
24 V DC
Current:
500 mA (max.)
B
10d
:
2
nd
position: 1 000 000
3
rd
position: 1 000 000
Actuating force:
from 1
st
position to 2
nd
position: 3 N typical
from 2
nd
position to 3
rd
position: 17 N typical
Galvanic isolation:
500 V AC to the rest