D3-DA 3xx/x
Technical data
Project engineering manual V1.07
98
© KEBA
12.8
Digital inputs
Input type:
Type 1 (according to EN 61131-2:2007)
Voltage range for HIGH:
18 V ≤ UH ≤ 28.8 V
Voltage range for LOW:
0 V ≤ UL ≤ 5 V
Galvanic isolation toward the control elec-
tronics:
Yes
Galvanic isolation of the inputs:
No
Cycle time (processing time):
1 ms
Filter:
Digital inputs: 500 Hz
Wiring:
Sink
Interrupt-driven inputs
Input type:
Type 1 (according to EN 61131-2:2007)
Voltage range for HIGH:
18 V ≤ UH ≤ 28.8 V
Voltage range for LOW:
0 V ≤ UL ≤ 5 V
Galvanic isolation toward the control elec-
tronics:
Yes
Galvanic isolation of the inputs:
No
Reaction time HIGH:
< +/- 0.75 us
Reaction time LOW:
< +/- 5.5 us
Wiring:
Sink