D3-DA 3xx/x
Mounting and installation instructions
Project engineering manual V1.07
32
© KEBA
Fig. 5-10: Connector mains filter
1
... Control module
2
... Supply module
3
... Axis module
4
... Earth potential
5
... Mains filter
6
... X01A (Line IN) connector
7
... Cable shield with shield clamp
8
... Grounded metallic base plate
Equipotential bounding lines
If the cabinet is not mounted directly on the machine or severals metres
away from the machine, it is recommended to install a equipotential bound-
ing line parallel to the cables, which are lead from the cabinet to the ma-
chine. The reason for this is, that because of switching processes and indi-
rect lightning strikes low-frequency high compensating currents can be cre-
ated, which may be too high for shieldings and especially for the shield con-
nectors and can so damage the shield connection.