This parameters are localized in the ModBus interface and determine their behaviour.
All operator parameters can be accessed as operator parameters via ModBus (mapping
lists only for 32 bit services) as well as via diagnosis interface (HSP5).

3.

Operator Parame-
ters

MDB_ProtCfg

0280h (FB.00)

5F00h

Meaning:

Configures the ModBus interface protocol configuration.

Data Length:

1 Byte

Coding:

B7

B6

B5

B4

B3

B2

B1

B0

RTU

/

ASCII

PARITY

Bit7:

=

1: ModBus RTU(binary) protocol

=

0: ModBus Ascii protocol (not yet adjustable)

Bit6, 5:

= 00: 8 data bits, no parity bit, 2 stop bit
= 01: 8 data bits, odd parity bit, 1 stop bit
= 10: 8 data bits, even parity bit, 1 stop  bit

Bit4, 3, 2, 1, 0 =

reserved for further use

Default Setting:

C0h: ModBus RTU, 8 data bits, even parity bit, 1 stop bit

Remarks:

A changed value will immediately be active and non-volatile saved.

MDB_SlavAddr_OP

0281h (FB.01)

5F01h

Meaning:

Defines the source for the ModBus slave address.

Data Length:

1 Byte

Coding:

255(dec): ModBus slave address

= SY.06. No ModBus activity if SY.06 = 0!

1...247:

ModBus slave address

= MDB_SlaveAddr_OP

Default Setting:

255(dec): ModBus slave address = SY.06.

Remarks:

A changed value will immediately be active and non-volatile saved.

MDB_MapStartAddr_Rd

0282h (FB.02)

5F02h

Meaning:

Configures the first parameter address whose read access is controlled by the read
mapping list.

Data Length:

2 Byte

Coding:

1

Default Setting:

0

Remarks:

A changed value will immediately be active and non-volatile saved.

MDB_MapStartAddr_Wr

0283h (FB.03)

5F03h

Meaning:

Configures the first parameter address whose write access is controlled by the write
mapping list.

Data Length:

2 Byte

Coding:

1

Default Setting:

0

Remarks:

A changed value will immediately be active and non-volatile saved.

Operator Parameters

Parameter name

Combivis Parameter address

ModBus-Register address

Legend

Содержание F5 COMBICOM ModBus

Страница 1: ...12 2003 CM F5 010 K000 BETRIEBSANLEITUNG INSTRUCTION MANUAL KEB COMBICOM ModBus...

Страница 2: ...Seite GB 3 GB 12 GB...

Страница 3: ...nctions 5 2 1 Slave Addressing 5 2 2 Parameter Addressing 5 2 3 ModBus Functions 6 2 4 User Defined Functions Defined By KEB 7 2 4 1 Function 100 Read Registers32 7 2 4 2 Function 101 Write Registers3...

Страница 4: ...3 RS232_RxD RS232 Rx Signal 4 RS485_RxD A RS485 Rx Signal A 5 RS485_RxD B RS485 Rx Signal B 6 VCC Power supply of the serial interface 7 GND Reference potential of the serial interface 8 RS485_TxD A R...

Страница 5: ...the diagnosis interface of the ModBus operator With an adapter the HSP5 cable is connected to the diagnosis interface see ordering informations When connected correctly access to all parameters of the...

Страница 6: ...32 bit parameters with the functions 3 4 16 Also the direct set addressing is supported here The beginning of the register addresses of the mapping lists is programmable with parameters MDB_MapStartA...

Страница 7: ...yte LoByte HiByte Number LoByte MSByte LSByte n Parameter Wert with Number Number of registers parameters to read with Start Addr First read register address Function 101 Response FUNC 101 dez Start A...

Страница 8: ...and non volatile saved MDB_SlavAddr_OP 0281h FB 01 5F01h Meaning Defines the source for the ModBus slave address Data Length 1 Byte Coding 255 dec ModBus slave address SY 06 No ModBus activity if SY 0...

Страница 9: ...t fieldbus watchdog by receive of each correct ModBus telegram to this slave broadcast included Default Setting 01h Remarks A changed value will immediately be active and non volatile saved Watchdog_A...

Страница 10: ...ode 3 illegal value if the values of the read parameter are not the same in all mapped sets MDB_Mapping_Wr_N see below 5F96h N COMBIVIS Para Addr COMBIVIS access through two parameters MDB_Write_MapIn...

Страница 11: ...ce HSP5_Max_InvBusy_Retries 0186h OS 06 not available Meaning Configures how often the ModBus operator repeats a request to the frequency inverter control if this answers with error code inverter busy...

Страница 12: ..._Mapping_Rd_0 4 5F95h 0289h 028Ah MDB_Mapping_Rd_99 4 5F96h 028Bh 028Ch MDB_Mapping_Wr_0 4 5FF9h 028Bh 028Ch MDB_Mapping_Wr_99 4 4 Annex 4 1 Table of Operator Parameters Error Code Meaning 1 Illegal f...

Страница 13: ......

Страница 14: ...tain Buisiness Park Morris Close Park Farm Wellingborough GB Northants NN8 6 XF fon 44 1933 402220 fax 44 1933 400724 net www keb uk co uk mail info keb uk co uk KEB Italia S r l Via Newton 2 I 20019...

Отзывы: