GB - 10

MDB_Mapping_Rd_N

see below

5F32h+N

COMBIVIS Para. Addr.:

COMBIVIS access through two parameters:
MDB_Read_MapIndex (0289h (FB.09)): = N
MDB_Read_Mapping (028Ah (FB.10)): The mapping itself

Meaning:

Configures the nte mapping for read access mapping. N = 0 referes to the first mapping.

Data Length:

4 Byte

Coding:

B0

B1

B2

B3

Para-Addr

HiByte LoByte

Para-Set Wlen

Para. Address: Parameter address (see application manual of the FI control).
Para. Set:

Parameter set bit coded

Bit0

= 1 --> Set 0 addressed

Bit7

= 1 --> Set 7 addressed.

Wlen: Data length = 16 bit words
Wlen = 1 --> Data length = 16 bit
Wlen = 2 --> Data length = 32 bit: In this case the first mapping for this parameter
contains the used mapping. In the following mapping the values of Para. Addr., Para.
Set and Wlen has to be set to zero. That means that a 32 bit mapping takes two entries
in the mapping list.

Remarks:

It is possible to address more than one set in one mapping. That means that the value
of Para. Set can have more then one bit set. Please keep in mind that in this case the
ModBus operator returns error code 3 (illegal value) if the values of the read parameter
are not the same in all mapped sets.

MDB_Mapping_Wr_N

see below

5F96h+N

COMBIVIS Para. Addr.:

COMBIVIS access through two parameters:
MDB_Write_MapIndex (028Bh (FB.11)): = N
MDB_Write_Mapping (028Ch (FB.12)): The mapping itself

Meaning:

Configures the nte mapping for write access mapping. N = 0 referes to the first mapping.

Data Length:

4 Byte

Coding:

Para. Addr.:

Parameter address (see application manual of the FI control).

Para. Set:

Parameter set bit coded

Bit0

= 1 --> Set 0 addressed

Bit7

= 1 --> Set 7 addressed.

Wlen: Data length = 16 bit words
Wlen = 1 --> Data length = 16 bit
Wlen = 2 --> Data length = 32 bit: In this case the first mapping for this parameter
contains the used mapping. In the following mapping the values of Para. Addr., Para.
Set and Wlen has to be set to zero. That means that a 32 bit mapping takes two entries
in the mapping list.

Remarks:

It is possible to address more than one set in write mapping. That means that the value
of Para. Set can have more then one bit set.

Operator Type

0180h (OS.00)

 

not available

Meaning:

Returns an identifier for the operator type.

Data Length:

2 Byte

Coding:

Internal KEB Coding:
10310(dec) = ModBus operator and diagnosis interface

Remarks:

Only for information

Operator Parameters

Содержание F5 COMBICOM ModBus

Страница 1: ...12 2003 CM F5 010 K000 BETRIEBSANLEITUNG INSTRUCTION MANUAL KEB COMBICOM ModBus...

Страница 2: ...Seite GB 3 GB 12 GB...

Страница 3: ...nctions 5 2 1 Slave Addressing 5 2 2 Parameter Addressing 5 2 3 ModBus Functions 6 2 4 User Defined Functions Defined By KEB 7 2 4 1 Function 100 Read Registers32 7 2 4 2 Function 101 Write Registers3...

Страница 4: ...3 RS232_RxD RS232 Rx Signal 4 RS485_RxD A RS485 Rx Signal A 5 RS485_RxD B RS485 Rx Signal B 6 VCC Power supply of the serial interface 7 GND Reference potential of the serial interface 8 RS485_TxD A R...

Страница 5: ...the diagnosis interface of the ModBus operator With an adapter the HSP5 cable is connected to the diagnosis interface see ordering informations When connected correctly access to all parameters of the...

Страница 6: ...32 bit parameters with the functions 3 4 16 Also the direct set addressing is supported here The beginning of the register addresses of the mapping lists is programmable with parameters MDB_MapStartA...

Страница 7: ...yte LoByte HiByte Number LoByte MSByte LSByte n Parameter Wert with Number Number of registers parameters to read with Start Addr First read register address Function 101 Response FUNC 101 dez Start A...

Страница 8: ...and non volatile saved MDB_SlavAddr_OP 0281h FB 01 5F01h Meaning Defines the source for the ModBus slave address Data Length 1 Byte Coding 255 dec ModBus slave address SY 06 No ModBus activity if SY 0...

Страница 9: ...t fieldbus watchdog by receive of each correct ModBus telegram to this slave broadcast included Default Setting 01h Remarks A changed value will immediately be active and non volatile saved Watchdog_A...

Страница 10: ...ode 3 illegal value if the values of the read parameter are not the same in all mapped sets MDB_Mapping_Wr_N see below 5F96h N COMBIVIS Para Addr COMBIVIS access through two parameters MDB_Write_MapIn...

Страница 11: ...ce HSP5_Max_InvBusy_Retries 0186h OS 06 not available Meaning Configures how often the ModBus operator repeats a request to the frequency inverter control if this answers with error code inverter busy...

Страница 12: ..._Mapping_Rd_0 4 5F95h 0289h 028Ah MDB_Mapping_Rd_99 4 5F96h 028Bh 028Ch MDB_Mapping_Wr_0 4 5FF9h 028Bh 028Ch MDB_Mapping_Wr_99 4 4 Annex 4 1 Table of Operator Parameters Error Code Meaning 1 Illegal f...

Страница 13: ......

Страница 14: ...tain Buisiness Park Morris Close Park Farm Wellingborough GB Northants NN8 6 XF fon 44 1933 402220 fax 44 1933 400724 net www keb uk co uk mail info keb uk co uk KEB Italia S r l Via Newton 2 I 20019...

Отзывы: