GB - 5

Value

Meaning

0

1200 Bit/s

1

2400 Bit/s

2

4800 Bit/s

3

9600 Bit/s

4

19200 Bit/s

5

38400 Bit/s

6

55500 Bit/s

1

1.2

ModBus Transmission
Speed

The ModBus transmission speed is adjusted through parameter SY.07 in the frequency
inverter control. During initialisation this value is read out by the ModBus operator
together with the inverter address and the value is taken as ModBus bitrate.

1:

No Default value of serial interfaces on Perso-
nal Computers

The KEB-ModBus operator is a slave interface. The required ModBus address for
addressing is determined by the operator parameter 

MDB_SlaveAddr_OP

. If the value

of the operator parameter is equal to 255(decimal), the ModBus address is taken from
the inverter address (SY.06). If SY.06 shall have the value zero which was reserved for
broadcast at ModBus, the ModBus operator disable all ModBus activities. If the values
are unequal 255(decimal) the ModBus address is directly taken from this value.

1.3

Diagnosis Interface

Attention !!!

To prevent the damage of the serial interface on your Personal Compu-
ter be sure that you use the special HSP5 cable from KEB for connecting
your PC to the diagnosis interface of the ModBus operator.

With an adapter the HSP5 cable is connected to the diagnosis interface (see ordering
informations). When connected correctly access to all parameters of the frequency
inverter is possible using the PC-software KEB Combivis. Also the operator internal
parameters can be read out and partly adjusted or parameterized with Download.

2.

Functions

2.1

Slave Addressing

The addresses of the parameters (register) are devided into different groups. Each of
this group has its own accessing method:

0000(hex).....1FFF(hex)

: This group is build up by those parameters that are accessed

through the mapping list. For a possible adaption of existing applications, the real
start of the mapping parameters in this range can be adjusted by parameters
MDB_MapStartAddr_Rd/Wr ‘. (see below).

2000(hex).....5EFF(hex)

: In this address area the parameters of the inverter control

board are mapped by a fixed algorithm. Access is always made on:

FI-Parameter Address = ModBus Register Address – 2000(hex). 

Please keep in

mind that in this address area access is done with indirect set addressing (with
FR.09). This means when writing/reading one parameter in different sets you have to
set the set indicator (FR.09) previously before access.

5F00(hex)....5FFF(hex): 

This block consists of the operator parameters.

2.2

Parameter Addressing

Functions

Содержание F5 COMBICOM ModBus

Страница 1: ...12 2003 CM F5 010 K000 BETRIEBSANLEITUNG INSTRUCTION MANUAL KEB COMBICOM ModBus...

Страница 2: ...Seite GB 3 GB 12 GB...

Страница 3: ...nctions 5 2 1 Slave Addressing 5 2 2 Parameter Addressing 5 2 3 ModBus Functions 6 2 4 User Defined Functions Defined By KEB 7 2 4 1 Function 100 Read Registers32 7 2 4 2 Function 101 Write Registers3...

Страница 4: ...3 RS232_RxD RS232 Rx Signal 4 RS485_RxD A RS485 Rx Signal A 5 RS485_RxD B RS485 Rx Signal B 6 VCC Power supply of the serial interface 7 GND Reference potential of the serial interface 8 RS485_TxD A R...

Страница 5: ...the diagnosis interface of the ModBus operator With an adapter the HSP5 cable is connected to the diagnosis interface see ordering informations When connected correctly access to all parameters of the...

Страница 6: ...32 bit parameters with the functions 3 4 16 Also the direct set addressing is supported here The beginning of the register addresses of the mapping lists is programmable with parameters MDB_MapStartA...

Страница 7: ...yte LoByte HiByte Number LoByte MSByte LSByte n Parameter Wert with Number Number of registers parameters to read with Start Addr First read register address Function 101 Response FUNC 101 dez Start A...

Страница 8: ...and non volatile saved MDB_SlavAddr_OP 0281h FB 01 5F01h Meaning Defines the source for the ModBus slave address Data Length 1 Byte Coding 255 dec ModBus slave address SY 06 No ModBus activity if SY 0...

Страница 9: ...t fieldbus watchdog by receive of each correct ModBus telegram to this slave broadcast included Default Setting 01h Remarks A changed value will immediately be active and non volatile saved Watchdog_A...

Страница 10: ...ode 3 illegal value if the values of the read parameter are not the same in all mapped sets MDB_Mapping_Wr_N see below 5F96h N COMBIVIS Para Addr COMBIVIS access through two parameters MDB_Write_MapIn...

Страница 11: ...ce HSP5_Max_InvBusy_Retries 0186h OS 06 not available Meaning Configures how often the ModBus operator repeats a request to the frequency inverter control if this answers with error code inverter busy...

Страница 12: ..._Mapping_Rd_0 4 5F95h 0289h 028Ah MDB_Mapping_Rd_99 4 5F96h 028Bh 028Ch MDB_Mapping_Wr_0 4 5FF9h 028Bh 028Ch MDB_Mapping_Wr_99 4 4 Annex 4 1 Table of Operator Parameters Error Code Meaning 1 Illegal f...

Страница 13: ......

Страница 14: ...tain Buisiness Park Morris Close Park Farm Wellingborough GB Northants NN8 6 XF fon 44 1933 402220 fax 44 1933 400724 net www keb uk co uk mail info keb uk co uk KEB Italia S r l Via Newton 2 I 20019...

Отзывы: