GB - 12
ModBus
COMBIVIS
Name
Data length
Address
Para. Address
in Byte
———
0180h
Operator Type
2
———
0182h
Software date
2
———
0183h
Diag Error Counter
2
———
0184h
DiagRsp.DelayTime
1
———
0185h
Diag Baudrate
1
———
0186h
HSP5_Max_InvBusy_Retries
1
———
0187h
HSP5 Tout Cnt
2
5F00h
0280h
MDB_ProtCfg
1
5F01h
0281h
MDB_SlaveAddr_OP
1
5F02h
0282h
MDB_MapStartAddr_Rd
2
5F03h
0283h
MDB_MapStartAddr_Wr
2
5F04h
0284h
MDB_MapNr_Rd
1
5F05h
0285h
MDB_MapNr_Wr
1
5F06h
0286h
Watchdog_Inhibit
1
5F07h
0287h
Watchdog_Activation
1
5F31h
0288h
MDB_Command
2
5F32h
0289h + 028Ah
MDB_Mapping_Rd_0
4
:
:
:
:
5F95h
0289h + 028Ah
MDB_Mapping_Rd_99
4
5F96h
028Bh + 028Ch
MDB_Mapping_Wr_0
4
:
:
:
:
5FF9h
028Bh + 028Ch
MDB_Mapping_Wr_99
4
4
Annex
4.1
Table of Operator
Parameters
Error Code
Meaning
1
Illegal function
2
Illegal data address
3
Illegal data value
4
Slave device failure
5
Function accepted but not yet finished
6
Slave device busy
64
Internal buffer overflow
65
Timeout at transfer to frequency inverter control
66
Parameter is write protected
67
Invalid password
4.2
Error Codes of
Exception Response
[1]: Modicon ModBus Protocol Reference Guide, PI-MBUS-300 Rev.J v. 06/1996
[2]: ModBus Application Protocol Specification V1.1 v. 12/06/02
[3]: ModBus over Serial Line Specification & Implementation Guide V1.0 v. 12/02/02