6.12.4 Example
For example, a user menu with following characteristics shall be programmed:
1. Display of actual set frequency (ru.3) in the set valid at the time
2. Adjustment of a fixed frequency (oP.22) in set 2
3. Adjustment of a fixed frequency (oP.22) in set 3
4. Acceleration and deceleration time (oP.11/oP.12) in the set active at the time
5. Energy-saving factor (uF.7) shall be adjustable in set 0
6. On switch-on the active parameter set (ru.18) shall be displayed
1.)
ud.15 = 2003
; Parameter address for ru.3
ud.16 = A
; Display in the active set
2.)
ud.17 = 2116
; Parameter address for oP.22
ud.18 = 2
; Preadjustment in set 2
3.)
ud.19 = 2116
; Parameter address for oP.22
ud.20 = 3
; Preadjustment in set 3
4.)
ud.21 = 210B
; Parameter address for oP.11
ud.22 = A
; Preadjustment in the set active at the time
ud.23 = 210C
; Parameter address for oP.12
ud.24 = A
; Preadjustment in the set active at the time
5.)
ud.25 = 2307
; Parameter address for uF.7
ud.26 = 0
; Preadjustment in set 0
6.
ud.27 = 2012
; Parameter address for ru.18
ud.28 = A
; Display in the active set
ud.2 = 1
; Display of ru-parameters (by activating the CP-mode this
setting is ignored)
ud.3 = 7
; Display of CP.7
adjust all other parameters to „off“ so that no indication occurs
6.12.5 Used Parameters
ud.0
2600h
✔
-
✔
0
9999
1
cp_on
-
ud.1
2601h
✔
-
-
-32767
32767
1
cp_on
only visible by bus
ud.2
2602h
✔
-
-
1(ru)
13 (LE)
1
ru
ru/oP/Pn/uF/dr/cn/ud/Fr/An/di/do/LE/In
ud.3
2603h
✔
-
-
0
*255
*1
1
* dependent on parameter group
ud.13
260Dh
-
-
-
-
-
-
-
only visible by bus
ud.14
260Eh
-
-
-
-
-
-
-
only visible by bus
ud.15
260Fh
✔
-
-
-1 (off)
7FFF
1
2003
corresponds to ru.3
ud.16
2610h
✔
-
-
0
8
1
0
set 0...7; A(8) = active set