KE2 Evap

OEM

Alarm Troubleshooting Guide

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Check wiring to the EEV terminal on the KE2 Evap OEM board. Refer below for prop-

er wiring of the KE2-RSV EEV and other common EEV wiring.

• The bare stranded wire of the EEV cable should be inserted so that the wire is 

directly touching the gate of the connector. If the gate is contacting the insulation 

of the wire, it will not allow the controller to correctly operate the valve. 

• If wires have been extended, check that colors have not been swapped.
• Measure resistance across the EEV leads. This will measure the resistance for 

the entire length of the lead wire, through the windings of the EEV and back to the 

other lead.

All values should be within 10% of stated values, otherwise indicating a wir-

ing issue. If absolutely sure of no wiring issue, the external coil may need to be 

replaced. For valves with internal windings, the valve may need to be replaced.
• If electrical diagnosis reveals no issues, and no system issues are present, there 

may be debris in the valve port. The valve can be driven open/closed several times 

through the manual control, while also lightly tapping the valve in an attempt 

to dislodge any debris. If valve has a strainer, strainer may need to be cleaned. 

Low Superheat Alarm Only
The Low Superheat Alarm is most commonly caused by the compressor failing to 

start/ compressor not running. There is a common misconception in the industry 

that the low pressure switch cut-in and cut-out pressure control on the condensing 

unit is set correctly for the application from the factory. 
The equipment manufacturers’ installation instructions recommend that the in-

stalling contractor adjust the low pressure cut-in and cut-out to recommended set-

tings for the application. The low pressure cut-in and cut-out set point should be 

set to either the ambient or space temperature, whichever is lower. 
When the controller calls for refrigeration, if suction pressure is not able to rise to 

the cut-in pressure before the EEV closes due to low superheat, the system will not 

start, and a Low Superheat Alarm triggered. 
Our technical support team typically sees an increase of these alarms in the fall 

when the ambient temperatures begins to decrease. If the low superheat alarm is 

intermittent, this is the most likely source of the alarm. Check the following:
• Low Pressure Control Pressure Switch. Reduce the cut-out pressure to meet the 

equipment manufacturer’s specification for the coldest ambient or box tempera-

ture, whichever is lower.

• Measure continuity across the low pressure control, if it indicates a closed cir-

cuit, next check the compressor start components and continue diagnosis at the 

condensing unit.

• Verify all fans are moving. Check if there is a mechanical service switch for the 

fans in the space being used inappropriately. If only one fan is not moving, verify 

whether the fan is operational. Replace the motor if necessary.

• Check fan motor rotational direction and fan blade pitch to ensure air is flow-

ing in the proper direction.

• Check for diminished load due to low air movement across the coil. This can 

be caused by excessive frost build-up on the coil on the air entering and/or air exit-

ing sides of the coil. The fans should be turned off while checking for frost buildup 

to allow a clear view of the coil. Product that is stacked too close to the coil and 

impedes airflow through the coil can also be a source of diminished load. 

• Check EEV and EEV wiring/cables – Please see previous steps.

M

OTOR

BLUE

ORANGE

YELLOW

RED

BLACK

M

OTOR

RED

GREEN

WHITE

BLACK

EEV

EMPTY

RSV

Check resistance across RSV leads:

Wire Colors

RSV-100 to 320 RSV-400 to 550

Blue – Orange

36 or 46 ohms

32 ohms 

Blue – Yellow 

36 or 46 ohms

32 ohms

Blue – Red 

36 or 46 ohms

32 ohms

Blue – Black 

36 or 46 ohms

32 ohms

For Sporlan SER-AA to L, measure:

Wire Colors

Black – White 

100 ohms

Red – Green 

100 ohms

Black – Green 

Open

Red – White 

Open

HSH / LSH Corrective Action - 

Continued

HSH / LSH Corrective Action - 

Continued

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: