KE2 EvapOEM Скачать руководство пользователя страница 10

KE2 Evap

OEM

Alarm Troubleshooting Guide

Q.1.61 January 2023

Page 10

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Troubleshooting Tables

Alarm & Alarm Name

Description

Variables & Setpoints Corrective Action

Basic 

Display

Combo 

Display

Web-

pages

HtA 

HtA

HIGH AIR 

TEMP

High Air 

Temp 

Alarm

Yellow LED is 

illuminated.

Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Return air temp is 

above Room Temp 

se Air Temp 

Diff + High Temp 

Alarm Offset for 

longer than High 

Temp Alarm Delay.

Example

Room Temp 

setpoint

20°F

Air Temp 

Diff

1°F

High Temp 

Alarm Offset

10°F

Alarm 

threshold 

temp

31°F

These setpoints can 

be adjusted by the 

user. The High Temp 

Alarm Offset factory 

default is 10.0°F for 

electric defrost and 

3.0°F for air defrost.

Variables

rtP - Room (Air) Temp

Setpoints

tS - Room Temp Set-

point

HAo - High Temp Alarm 

Offset

HAd - High Temp Alarm 

Delay

Investigate condition. The majority of high temperature alarms are not related to the 

controller. To resolve the High Air Temp Alarm will require basic refrigeration trouble-

shooting.
• Ask staff if the door has been propped open for an extended period of time due to 

loading, unloading, inventory, etc. If this is not the case, begin to troubleshoot the 

system.

• Check air sensor.
• Check the evaporator coil to verify the coil is free from excessive frost.
• Check the fans to ensure all fans are rotating properly. 
• Check compressor operation.
• Check for proper refrigerant charge.
• Make sure the system has sufficient capacity.
• If pressure transducer and suction temperature sensor are installed, check superheat 

and investigate if superheat is abnormally high.

• Troubleshoot TEV or EEV (if installed, see high superheat corrective actions on the 

previous pages).

Note: High Temp Alarm is not triggered during defrost.

LtA

LtA

 

LOW AIR 

TEMP

Low Air 

Temp 

Alarm

Yellow LED is 

illuminated. 

Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Return air temp is 

below Room Temp 

setpoint - Low Temp 

Alarm Offset for 

longer than Low 

Temp Alarm Delay.
The default alarm 

condition is 4°F 

below the Room 

Temp setpoint for 

10 minutes, but 

can be adjusted as 

necessary.

Variables

rtP - Room (Air) Temp
Setpoints

tS - Room Temp Set-

point

LAo - Low Temp Alarm 

Offset 

LAd - Low Temp Alarm 

Delay

• Verify the system will pumpdown. This can be done in multiple ways; the easiest is 

to initiate a defrost from the Basic Display. Press and hold the 

 and 

 

until ddF 

(defrost delay fan) or dEF (defrost) is displayed. Liquid line solenoid should close im-

mediately, if not, troubleshoot the solenoid and the wiring controlling the solenoid. 

Solenoid should shut tightly and not allow liquid refrigerant through. If the system 

only has an EEV, the EEV should also shut tightly during the defrost.

• Check that the low pressure control is set, and operating properly.
• Check the tS (room temperature setpoint), LAo (low alarm offset), and LAd (low 

temp alarm delay) settings.

• If there are multiple systems in the room, check the room temperature setpoint of 

the other systems.

• Check for outside air infiltration. Example: Infiltration from freezer into cooler.

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: