KE2 Evap

OEM

Alarm Troubleshooting Guide

Q.1.61 January 2023

Page 12

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Troubleshooting Tables

Alarm & Alarm Name

Description

Variables & Setpoints Corrective Action

Basic 

Display

Combo 

Display

Web-

pages

CoA 

CoA

COMMU-

NICATION 

ERROR

Network 

Comms 

Alarm

ONLY ACTIVE FOR 

BONDED CONTROL-

LERS.
Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present. 
No communication 

between controllers 

for one minute or 

more. 

Variables

iP1 - IP Address Part 1

iP2 - IP Address Part 2

iP3 - IP Address Part 3

iP4 - IP Address Part 4

• Communication, Lead/Lag, and Compressor Sequencer Communications Alarms are 

most commonly caused by local network issues.

• Verify all network switches are connected and functioning properly. Check that all 

controllers in a bonded group, lead/lag pair, or compressor sequencer group are 

powered up.

• Verify communication to each individual controller using whatever method is usually 

used to communicate to the controllers in question (via IP address, KE2 SmartAccess 

etc.). If one or more are unreachable, investigate those controllers and their network 

cabling further. 

• Ensure all cables are inserted fully into their respective jacks. Check for any damaged 

cable.

• On new installations, where the cables are built in the field, check network cables for 

proper wire color code (Ethernet standard A or B, see Q.5.5 Making Ethernet Cable for 

more information). Also make sure copper for each wire goes fully into the clip. If one 

or more wires is out of order or doesn’t fully insert into the clip, it needs to be fixed 

before it can be used to communicate.

• Attempt to unbond and re-bond the controllers or unpair/re-pair for lead/lag (re-

member to re-enable Lead/Lag mode after re-pairing). If any of the controllers are 

not discoverable from the Network page, investigate those controllers further.

CLL

CLL

LEAD/LAG 

COMM 

ERROR

Lead/Lag 

Comms 

Alarm

ONLY ACTIVE FOR 

LEAD/LAG CONTROL-

LERS.
Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present. 
Communication lost 

between lead/lag 

controllers.

CCA 

CCA

COMP SEQ 

COMM 

ERROR

CompSeq. 

Comms 

Alarm

ONLY ACTIVE WHEN 

SITEVIEW IS ACTIVE.
Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Communication lost 

to KE2 Compressor 

Sequencer OEM.

EFL

EFL

EMAIL 

FAILURE

Email 

Failure 

Alarm 

Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Email alert was not 

confirmed by email 

server provided after 

seven consecutive 

attempts.

Variables

iP1 - IP Address Part 1 

iP2 - IP Address Part 2 

iP3 - IP Address Part 3 

iP4 - IP Address Part 4

Setpoints 

dHC - DHCP mode

• Ensure the controller has Internet access. If possible plug a laptop into the Ethernet 

cable at the controller to test Internet connection. 

• Check the Network Info settings (gateway, DNS etc.) on the controller’s Network 

webpage. If DHCP is enabled on the controller these settings should be provided 

automatically to the controller by the local network.

• Email Failure Alarm is a function of the controller attempting to send out an email 

alert using the information entered in the Alert Notifications section of the Settings 

Page, and failing to communicate successfully with the email server provided. If us-

ing a custom email server, consider using the KE2 Therm Default Server instead. 

• Servers requiring basic authentication should provide User name and Password, 

and ensure it is correctly entered. 

• Servers without authentication requirements should not enter information in the 

User name or Password field. If unsure of server requirements and alarm occurs, 

ensure both User name and Password are blank and retry. 

• Check the Time Reference Options on the setpoints page of the controller webpage. 

This is found under general information. If set to “Custom” ensure the web address 

provided is a valid SNTP server. Alternatively, change the setting to “Internet” to use 

a predefined SNTP server or “Local” to rely on the local web browser to update the 

time.

ntP

ntP

TIMER 

SERVER 

COMM

Time 

Server 

Comm

Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Controller cannot 

communicate with 

external time of day 

server (SNTP server).

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: