KE2 EvapOEM Скачать руководство пользователя страница 5

Q.1.61 January 2023

Page 5

KE2 Evap

OEM

Alarm Troubleshooting Guide

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Troubleshooting Tables

Alarm & Alarm Name

Description

Variables & Setpoints Corrective Action

Basic 

Display

Combo 

Display

Web-

pages

PSA 

PSA

PRESSURE 

SENSOR

Suc Pres 

Sensor 

Alarm

ONLY ACTIVE 

WHEN AN ELECTRIC 

EXPANSION VALVE IS 

SELECTED.
Red LED is 

illuminated.
Suction pressure 

sensor is shorted, 

open, or pressure is 

out of range.
EEV cannot operate 

while this alarm is 

present.

Variables

PrS - Suction Pressure

Setpoints

rFG - Refrigerant
•Suction pressure will 

read -14.6 if the green 

input (signal) is open or 

disconnected.

•Suction pressure will 

read 150* or over if the 

green input (signal) 

is shorted, or if actual 

pressure is higher than 

the transducer is rated 

for. 

*150, 300, or 750 

psig depending on 

refrigerant selected.

The majority of sensor alarms and inaccurate readings are caused by cut, burned, 

chaffed or otherwise damaged sensor cables. Inspect the length of the cable for any 

burned, chaffed or otherwise damaged sections. Repair any damaged sections; take 

care not to swap colors when repairing.
• Confirm that a KE2 Therm pressure transducer and cable are being used. KE2 Therm’s 

pressure transducer cable will have red, black, and green leads.

• Check that the pressure transducer cable wires are inserted into the proper position 

on the board (gray connector) and that the colors are inserted into the proper screw 

down terminals. The bare stranded wire of the transducer cable should be inserted so 

that the wire is directly touching the gate of the connector. If the gate is contacting the 

insulation of the wire, it will not allow the controller to read the sensor.

• If wires have been extended, check that colors have not been swapped when extended. 

Check for any bad splices, crimps or solder joints where extended.

• Check that the pressure transducer cable is fully inserted into the pressure transducer. 

The cable should click when fully inserted into the transducer.

• Confirm that the proper transducer is being used for the system. 0-150psia for most 

common refrigerants, 0-300psig for R-410A and 0-750psig for R-744 (CO2). Confirm 

that the proper refrigerant (rFG) is selected in the setpoints menu.

• To verify the accuracy of the transducer, remove the transducer from the system. The 

controller should read suction pressure as approximately 0 psig when measuring 

atmosphere.  The transducer can also be checked against your manifold set.

Note: If PrS shows -15 when transducer is measuring atmosphere, the wrong pressure 

transducer/refrigerant combination has been selected.

• Verify the voltage between the black and red pressure transducer inputs on the 

controller is +5 VDC.

• Measure the voltage between the black and green inputs on the controller. Enter that 

number into the following formula:

(voltage read - 0.5V) x 150*psia = actual pressure read 

(verify with gauges)

4v

* 300 psig or 750 psig depending on pressure transducer range.

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: