KE2 EvapOEM Скачать руководство пользователя страница 16

KE2 Evap

OEM

Alarm Troubleshooting Guide

Q.1.61 January 2023

Page 16

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Troubleshooting Tables

Alarm & Alarm Name

Description

Variables & Setpoints Corrective Action

Basic 

Display

Combo 

Display

Web-

pages

LPA

LPA

LOW PRES-

SURE

Low 

Pressure 

Alarm

Suction pressure 

below Low Pressure 

Cut-out despite at-

tempts to run.

Variables

PrS – Suction Pressure

Setpoints

LPC – Low Pressure 

Cut-out

• Check LPC to see if the Low Pressure Cut-out is set too high.  LPC should be set to 

refrigeration unit manufacturer’s recommendation.

• Check for restrictions in the liquid line.
• Confirm EEV is operating properly.  See High/Low Superheat corrective actions for 

troubleshooting the EEV.

KE2 Humidity Control Only

HSA

HSA

HUMIDITY 

SENSOR

Humidity 

Sensor 

Alarm

Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Humidity sensor is 

shorted or open.

Variables

HU - Humidity

• The majority of sensor alarms and inaccurate readings are caused by cut, burned, 

chaffed, or otherwise damaged sensor cables. Inspect the length of the cable for any 

burned, chaffed, or otherwise damaged sections. Repair or replace any damaged sec-

tions; take care not to swap colors when repairing.

 • Check that the humidity sensor cable wires are inserted into the proper terminals on 

the KE2 Humidity Control, and that the screw down terminals are screwed down. The 

bare stranded wire of the cable should be inserted so that the wire is directly touch-

ing the gate of the connector. If the gate is contacting the insulation of the wire, it will 

not allow the controller to read the sensor.

• If wires have been extended, check that colors were not swapped when extended.  

Check for any bad splices, crimps, or solder joints where extended.

• Verify the voltage between the red and black humidity sensor inputs on the control-

ler is approxi14 VDC.

• Measure the voltage between the black and green inputs on the controller. Enter that 

number into the following formula:

(voltage read / 5VDC) x 100 = humidity reading

HHA

HHA

HIGH 

HUMIDITY

High 

Humidity 

Alarm

Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Humidity reading 

is above Humidity 

Se Humidity 

Differ Humid-

ity Alarm Offset for 

longer than the Hu-

midity Alarm Delay.

Variables

HU – Humidity

Setpoints

HSP – Humidity Set-

point

HdP – Humidity Dif-

ferential

UAo – Humidity Alarm 

Offset

UAd – Humidity Alarm 

Delay

HEt – Heater setpoint

HEd – Heater Differen-

tial setpoint

dto – Dehumidity Temp 

Offset

USt – Max Superheat

• The humidity sensor should be located in an area representative of the controlled 

space. Avoid large openings to the space as they have the potential to read higher 

than the rest of the space. The senor must be placed with the metal cylinder in the 

downward direction to read accurately.

• Confirm that any dehumidification, humidification, and/or reheat devices are operat-

ing as expected.

• Address any sources of infiltration to reduce the amount of humidity being intro-

duced to the space. 

• Check drain pan and drain line for any clogs.
• Confirm Electric Expansion Valve (EEV) and refrigeration system is operating as ex-

pected. See High/Low Superheat Alarm corrective actions for troubleshooting the 

EEV.

• Increase the Max Superheat setpoint to increase runtime.  Do not allow superheat at 

the compressor to exceed the manufacturer’s recommended maximum.

• If system is satisfying on temperature before humidity target is reached, the Dehu-

midify Offset can be decreased.  Do not allow room to over-cool to the point it dam-

ages product.

• If system is satisfying on temperature before humidity target is reached, additional 

reheat or dehumidifiers may be required.  Defrost heaters should not be used for 

reheat, as it does not allow the coil to reach dew point and extract moisture, leading 

to higher humidity.

• For systems with electric defrost, increase the number of defrosts per day.
• If you believe the humidity reading may be in error, proceed to troubleshooting steps 

for Humidity Sensor Alarm.

Humidity

Sensor

RED (+14VDC)

GREEN (SIG)

BLACK (0VDC)

GND

0-5

+12

EMPTY

– LPCO (Low Pressure Cut-Out control) Only

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: