KE2 EvapOEM Скачать руководство пользователя страница 8

KE2 Evap

OEM

Alarm Troubleshooting Guide

Q.1.61 January 2023

Page 8

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Troubleshooting Tables

Alarm & Alarm Name

Description

Variables & Setpoints Corrective Action

Basic 

Display

Combo 

Display

Web-

pages

HSH 

HSH

HIGH SU-

PERHEAT

High Su-

perheat 

Alarm

Yellow LED is 

illuminated. 

Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
[EEV] Superheat 

reading 2°F above 

superheat setpoint 

for 90 minutes of 

cumulative runtime, 

and valve > 90% 

open. 
[TEV] Superheat 

reading above 

superheat setpoint 

for 90 minutes of 

cumulative runtime.

Variables

SHt - Superheat

PrS - Suction Pressure

SUt - Suction Temp

oPn - Valve % Open

Setpoints

rFG - Refrigerant

Edt - Expansion Device 

Type

• Check the system suction pressure using either the Basic Display (PrS), or the con-

troller’s browser interface. Validate the suction pressure is within the range of the system 

design. If a new install, confirm valve is properly sized for the system under all operating 

conditions.

• Check refrigerant type. Press and hold 

 until tS appears. Press 

 

to rFG (refriger-

ant). Press 

 to see the currently selected refrigerant. To change refrigerant press 

until the correct refrigerant is shown. Press and hold 

 to save correct refrigerant 

type. To exit the menu press 

.

• Check valve type. Press and hold 

 until tS appears. Press 

 

to Edt (expansion de-

vice type). Press 

 to see currently selected valve. To change the valve type press 

 

until the correct valve is shown. Press and hold 

 to save. Controller will reboot. Con-

firm proper system operation with the variables menu.

• If system operation has not improved, re-initialize the valve. This can be done by click-

ing the “Reboot” button on the Setpoints page under General Information in the brows-

er interface, or power may be cycled to the controller.

 Check the valve position in the variables menu (oPn). If the valve is fully open, verify 

the valve is operating properly by manually operating the valve from the Basic Dis-
play. Press 

 and   at the same time on the Basic Display until a number with 

the right most number blinking displays. This is the valve percent open, and the EEV 
is now under manual control. Press 

 

to open and   to close the valve. Press 

 

momentarily to change how much the valve opens with each button press (0.1%, 1.0% 

or 10.0%). The valve should start to move immediately to the position indicated on the 

display. While verifying suction pressure either from the controller’s browser interface 

or with gauges, begin closing the valve 10.0% at a time. The suction pressure should 

decrease somewhat with each 10% closure. Completely close the valve to 0.0%; system 

should pump down. If suction pressure responds to closing the valve, valve should be 

operating correctly and a system issue is likely present: low charge, restriction in the 

liquid line, dirty condenser etc. If suction pressure does not respond to manually oper-

ating the valve, proceed to next step.

LSH 

LSH

LOW SU-

PERHEAT

Low Su-

perheat 

Alarm

Yellow LED is 

illuminated. 

Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Superheat reading 

below 3°F for 5 

minutes and EEV < 

10% open if EEV is 

selected.

Refrigerants

Abbreviation Full Name

Abbreviation Full Name

R22

R-22

449

R-449A

134

R-134a

448

R-448A

42d

R-422D

744

R-744

42A

R-422A

410

R-410A

40C

R-407C

407

R-407F

40A

R-407A

409

R-409A

507

R-507

408

R-408A

404

R-404A

438

R-438A

458

R-458A

717

R-717

513

R-513A

452

R-452A

450

R-450A

Valve Types

Basic Display

KE2 Combo Display

Description

Abbreviation Scrolling Text

tHr

tHr

MECHANICAL

Thermostatic Expansion Valve (TEV).

PLS

PLS

PULSE VALVE

Pulse Width Modulation (PWM) Valve.

rS

rS 

KE2 RSV

KE2 Therm’s Refrigeration Stepper Valve.

SEi

SE

i

SER/SEI 1 TO 20

12VDC Bipolar Sporlan EEV with 1,600 

max steps, 200 steps/second.

SEr

SEr

SER AA TO L

12VDC Bipolar Sporlan EEV with 2,500 

max steps, 200 steps/second.

CrL

CrL

CAREL

12VDC Bipolar Carel EEV with 480 max 

steps, 50 steps/second.

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: