KE2 EvapOEM Скачать руководство пользователя страница 7

Q.1.61 January 2023

Page 7

KE2 Evap

OEM

Alarm Troubleshooting Guide

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

21214V3.0

Troubleshooting Tables

Alarm & Alarm Name

Description

Variables & Setpoints Corrective Action

Basic 

Display

Combo 

Display

Web-

pages

EdF 

EdF

EXCESS 

DEFROST

Excess 

Defrost 

Alarm

Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Time between 

defrosts too short in 

demand defrost.

Variables

CLt - Coil Temp

DEr - Defrost Relay

Setpoints

dtY - Defrost Type

ind - Initiate Defrost 

Mode

dtP - Defrost Term Temp

Excess Defrost Alarm and Defrost Termination on Time Alarm are closely linked; 

both indicate issues with the defrost process/defrost heat. Excess defrost alarm only 

occurs when using defrost based on evaporator efficiency (demand).
Air/ Electric / Hot Gas Defrost - Check solenoid valve. While the controller is in 

refrigeration or satisfied on temperature, initiate a defrost from the Basic Display by 

pressing and holding the 

 and 

 

until ddF (defrost delay fan) or dEF appears. 

The solenoid valve should close and the flow of liquid refrigerant to the evaporator 

should be stopped for the entire defrost.
Note: For electric and hot gas defrost, the controller should run fans only for several 

minutes while the system pumps down in ddF (defrost delay Fan) mode. In ddF

solenoid valve and heaters should be off. The display will change to dEF (defrost) after 

the fan operation is complete. Fans should turn off, solenoid valve should remain off, 

and all heaters should turn on.
Electric Defrost - Verify that the heaters are working properly. Measure amperage of 

the heaters while heaters are energized and check that it matches the nameplate of 

the evaporator. If less than the nameplate, check for damaged heaters and any cut, 

burned, chaffed or disconnected wires in the heater circuit. Repair damage and check 

for proper defrost operation.
Note: Toward the end of the defrost cycle, the controller periodically turns heaters off 

to reduce steaming and overall heat of defrost.
Air/ Electric / Hot Gas Defrost - Verify coil sensor location. An excessive number 

of defrosts is often due to coil sensor location. The coil sensor, or sensors, serve as 

defrost termination sensors. If in an improper location (such as close to a heater), or 

if a coil sensor has been pulled out, defrost will terminate too soon or will take too 

long to terminate. The controller will respond by initiating another defrost shortly 

after the irregular defrost, and the cycle will continue until the Excess Defrost Alarm 

is triggered. Relocate the coil sensor to where frost has built up the heaviest on the 

coil and initiate a defrost. Check to make sure the defrost terminates in a reasonable 

amount of time (less than 30-35 minutes for air defrost, less than 18-22 minutes for 

electric defrost) and the coil is completely clear of frost. If there is any frost remaining 

on the coil after the defrost, relocate a coil sensor to that location. The proper location 

for the coil sensor is always the last place frost disappears.
Air/ Electric / Hot Gas Defrost - Verify door has not been left open for an extended 

period. Add door switch (PN 20543) to reduce excess frost caused by door openings.
Air/ Electric – Cold air from an evaporator in refrigeration in the same space may 

prevent a defrosting coil from reaching termination temperature within a reasonable 

amount of time. Bonding and synchronizing defrost on the evaporators allows the 

evaporators to defrost more quickly. See Q.1.45-A Multi Evap Applications for more 

information on bonding.
Air Defrost - The KE2 Evap OEM keeps the room temperature much tighter than is 

typically seen in the industry. The KE2 Evap OEM’s default air temperature differential 

is 1.0°F, while the system is still protected from short cycling by minimum off and 

minimum run times if temperature fluctuation is larger than normal. If the room 

temperature setpoint on the KE2 Evap OEM is set to the same temperature cut-out 

as traditional mechanical controls where differentials of 4.0°F or 5.0°F are common, 

it will result in a much colder room temperature on average. Consider this when 

setting the room temperature setpoint. If receiving Defrost Termination on Time or 

Excess Defrost Alarm with air defrost, the room air heat alone may not be sufficient to 

complete the air defrost. The room temperature setpoint should be raised, or electric 

heat added to the evaporator. Alternatively, dtP (defrost term temp) can be lowered 

to one degree above rTP (room temp), however, the coil sensor MUST be in the spot 

on the coil where frost disappears last during defrost to ensure a completely clean coil 

after every defrost. Otherwise, set ind (initiate defrost mode) to SCH (schedule), and 

set dPd (defrost per day) and dtL (defrost time length) to the number of times per 

day and length of defrost needed to completely clear the coil of frost. If the maximum 

defrost time is still not sufficient to clear the coil of frost, the Defrost Termination on 

Time Alarm will continue to trigger.
Return Defrost Mode to Demand after resolving the issue.

dtt 

dtt

DEFR TERM 

ON TIME

Defr 

Term 

on Time 

Alarm

Yellow LED is illumi-

nated. Controller will 

attempt to continue 

to operate system 

while this alarm is 

present.
Defrost terminated 

on time instead of 

temperature for two 

consecutive defrosts.

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: