KE2 EvapOEM Скачать руководство пользователя страница 1

© Copyright 2023 KE2 Therm Solutions, Inc., Washington, Missouri 63090

KE2 Evap

OEM

Alarm Troubleshooting Guide

Q.1.61  January 2023

therm

solutions

21214V3.0

Users are notified of alarms in multiple ways, described below.
From the face of the Basic Display:

The alarm is shown as a three digit code on the Basic Display, and the yel-

low or red LED light on the right side of the display will illuminate. If there 

is more than one alarm present at the same time, press  to cycle through 

the alarms.

Alarm Severity:

Red LED: 

Critical Alarm

 - The controller will close the electric 

expansion valve (EEV) to prevent compressor damage. This will 

likely prevent refrigeration from continuing, but the con-

troller is attempting to prevent a catastrophic system fail-

ure, such as damage to the compressor. Critical alarms 

must be addressed immediately.

Yellow LED:

 Cautionary Alarm

 - The controller will con-

tinue to function to the best extent possible given the 

system conditions, but the alarm should be addressed 

as soon as possible.
On the controller’s webpage:

Alarms can also be viewed in the top right-hand side of 

the controller’s webpage as a pulsing yellow or red bell 

when connected to the controller via a smart device (smartphone, tablet, 

PC etc.), or remotely via KE2 SmartAccess. When not in alarm, no bell is dis-

played.

If the controller is connected to the internet, the KE2 Evap OEM can also send 

text messages and/or emails to immediately notify all necessary personnel 

of the alarm condition.
Alarm thresholds such as high temp and door alarm can be adjusted, and 

should be set so as not to trigger 

during normal loading and use.
Almost all alarms will automati-

cally clear once the alarm con-

dition no longer exists. To clear 

an alarm manually, press and 
hold 

 until tS (temperature 

Setpoint) appears, press   sev-

eral times to CLA (CLear Alarm), 
press and hold 

 until the 

red LED blinks, then release. 

Power cycling the controller to 

clear alarms is not recommend-

ed, but will also reset the alarm 

conditions.
Clearing alarms before calling 

technical support will make 

diagnosis more difficult or im-

possible; please call technical 

support before clearing alarms 

if assistance is required.
Note:  
If the alarm is a sensor 

alarm and the sensor is still dis-

connected or shorted, the alarm 

will immediately reappear.

Troubleshooting:

Video 034 – Iced Evaporator Coil on a Walk-in Freezer

Video 044 – Iced Evaporator Coil on a Walk-in Cooler

Video 107 – Troubleshooting a Temperature Sensor

Video 106 – Troubleshooting a Pressure Transducer

Introduction:

The KE2 Evap OEM has advanced communications and alarming features, never 

before seen in the refrigeration industry. These alarms provide early indications of 

a poorly performing refrigeration system.
Text messages and/or email alerts provide notification of system issues 

immediately, whether on-site or remote, as long as there is an internet connection.
Advanced alarming, diagnostic and troubleshooting are key features of the 

KE2 Evap OEM controller, and help prevent catastrophic failures. This protects 

contractor, owner, product, and refrigeration equipment.

When using KE2 SmartAccess, the controllers can be viewed, setpoints changed, and defrosts initiated remotely; saving time and frustration. In addition, 

your home office or KE2 Therm technical support can even login with you to diagnose the system in real time.

Alarm Notifications:

Basic setup:

Video 068 – How to Determine Proper Coil Sensor Location

Video 069 – How to Properly Install a Coil Sensor

These videos are relevant when troubleshooting 
or for basic setup of your controller.

Содержание EvapOEM

Страница 1: ...con dition no longer exists To clear an alarm manually press and hold until tS temperature Setpoint appears press sev eral times to CLA CLear Alarm press and hold until the red LED blinks then releas...

Страница 2: ...2 F above superheat setpoint for 90 minutes of cumulative runtime and valve 90 open TEV Superheat above SUPERHEAT setpoint for 90 minutes of cumulative runtime Page 8 9 LSH LSH LOW SUPERHEAT Low Super...

Страница 3: ...Display panic button is active Page 15 LPCO Low Pressure Cut Out control Only Pdt Pdt PUMPDOWN TIMEOUT Pump Down Timeout Low Pressure Cut out Time exceeded before suction pressure reached Low Pressur...

Страница 4: ...display going blank and other unexpected problems Power over Ethernet POE switches connected to the KE2 Evap OEM should have the power output feature disabled Ed Ed ELECTRIC DEFROST TEV Intro Ed is b...

Страница 5: ...on the board gray connector and that the colors are inserted into the proper screw down terminals The bare stranded wire of the transducer cable should be inserted so that the wire is directly touchin...

Страница 6: ...of the connector If the gate is contacting the insulation of the wire it will not allow the controller to read the sensor If wires have been extended check for any bad splices crimps or solder joints...

Страница 7: ...triggered Relocate the coil sensor to where frost has built up the heaviest on the coil and initiate a defrost Check to make sure the defrost terminates in a reasonable amount of time less than 30 35...

Страница 8: ...If the valve is fully open verify the valve is operating properly by manually operating the valve from the Basic Dis play Press and at the same time on the Basic Display until a number with the right...

Страница 9: ...ace temperature whichever is lower When the controller calls for refrigeration if suction pressure is not able to rise to the cut in pressure before the EEV closes due to low superheat the system will...

Страница 10: ...refrigerant charge Make sure the system has sufficient capacity If pressure transducer and suction temperature sensor are installed check superheat and investigate if superheat is abnormally high Tro...

Страница 11: ...ector If the gate is contacting the insulation of the wire it will not allow the controller to read the door switch Inspect the length of the cable for any cut burned chaffed or otherwise damaged wire...

Страница 12: ...e system while this alarm is present Communication lost between lead lag controllers CCA CCA COMP SEQ COMM ERROR CompSeq Comms Alarm ONLY ACTIVE WHEN SITEVIEW IS ACTIVE Yellow LED is illumi nated Cont...

Страница 13: ...rm Alarm Name Description Variables Setpoints Corrective Action Basic Display Combo Display Web pages dtS dtS DOORTEMP SENSOR Door Temp Sensor Alarm Combo Display Aux 1 Door Temp Sensor is shorted or...

Страница 14: ...ded on the controller DOOR TEMP SENSOR is the blue connector labeled TEMP1 If incorrect sensor is wired in re wire to correct position See if DISP HEATER RELAY in theVARIABLES menu is showing heater O...

Страница 15: ...he input s functionality If the controller is alarming when the external device is not active changing the state will reverse the logic EA2 EA2 DISPLAY EXTERNAL ALARM 2 Disp Ext2 Alarm EA3 EA3 DISPLAY...

Страница 16: ...er that number into the following formula voltage read 5VDC x 100 humidity reading HHA HHA HIGH HUMIDITY High Humidity Alarm Yellow LED is illumi nated Controller will attempt to continue to operate s...

Страница 17: ...Discharge Delay NSt Max Number of Starts Proceed to corrective actions for High Disch Temp alarm Must be manually cleared by clearing alarms or cycling power TroubleshootingTables Alarm Alarm Name De...

Страница 18: ...low Cond Temp setpoint Low Cond Temp Alarm Offset for lon ger than Low Cond Temp Alarm Delay Variables AU1 AU2 AU3 Con denser Temp any Aux Input can be set to Cond Temp Setpoints Cdt Cond Temp Setpoin...

Отзывы: