V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
91
Table 2-7.10: KMF-160 DVN4 heating capacity(continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-13.7
-15
10.40
4.84
9.71
4.60
9.03
4.41
8.63
4.23
8.29
4.10
7.60
3.78
-11.8
-13
10.40
4.67
9.71
4.43
9.03
4.24
8.63
4.09
8.29
3.93
7.60
3.61
-9.8
-11
10.40
4.52
9.71
4.26
9.03
4.04
8.63
3.90
8.29
3.76
7.60
3.48
-9.5
-10
10.40
4.36
9.71
4.09
9.03
3.87
8.63
3.73
8.29
3.60
7.60
3.29
-8.5
-9.1
10.40
4.18
9.71
3.94
9.03
3.71
8.63
3.57
8.29
3.44
7.60
3.10
-7
-7.6
10.40
4.02
9.71
3.77
9.03
3.58
8.63
3.45
8.29
3.31
7.60
2.97
-5
-5.6
10.40
3.87
9.71
3.64
9.03
3.40
8.63
3.31
8.29
3.18
7.60
2.82
-3
-3.7
10.40
3.74
9.71
3.49
9.03
3.25
8.63
3.18
8.29
3.04
7.60
2.72
0
-0.7
10.40
3.59
9.71
3.35
9.03
3.11
8.63
3.02
8.29
2.90
7.60
2.67
3
2.2
10.40
3.42
9.71
3.19
9.03
2.99
8.63
2.90
8.29
2.75
7.60
2.66
5
4.1
10.40
3.25
9.71
3.06
9.03
2.88
8.63
2.77
8.29
2.69
7.60
2.63
7
6
10.40
3.10
9.71
2.93
9.03
2.74
8.63
2.66
8.29
2.65
7.60
2.56
9
7.9
10.40
3.05
9.71
2.86
9.03
2.70
8.63
2.60
8.29
2.54
7.60
2.47
11
9.8
10.40
3.00
9.71
2.82
9.03
2.63
8.63
2.53
8.29
2.49
7.60
2.43
13
11.8
10.40
2.91
9.71
2.72
9.03
2.55
8.63
2.48
8.29
2.44
7.60
2.38
15
13.7
10.40
2.87
9.71
2.67
9.03
2.47
8.63
2.42
8.29
2.37
7.60
2.31
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.