3 Refrigerant Piping Design
3.1 Design Considerations
Refrigerant piping design should take account of the following considerations:
The
amount of brazing required should be kept to a minimum.
On the
two inside sides of the first indoor branch joint (“A” in Figures 3-3.4 and Figure 3-3.5) the system should, as far
as possible, be equal in terms of number of units, total capacities and total piping lengths.
3.2 Material Specification
Only seamless phosphorus-deoxidized copper piping that complies with all applicable legislation should be used. Temper
grades and minimum thicknesses for different diameters of piping are specified in Table 3-3.1.
Table 3-3.1: Piping temper and thickness
Piping outer diameter
(mm)
Temper
1
Minimum thickness
(mm)
Ф6
.35
O
(annealed)
0.8
Ф9
.53
0.8
Ф12
.7
0.8
Ф15
.9
1.0
Ф19
.1
1.0
Ф22
.2
1/2H
(half hard)
1.2
Ф25
.4
1.2
Ф28
.6
1.3
Ф
31.8
1.5
Ф38
.1
1.5
Ф
41.3
1.5
Ф44
.5
1.5
Ф54
.0
1.8
Notes:
1. O: coiled piping;
2. 1/2H: straight piping.
3.3 The Permitted Piping Lengths and Level Differences
The piping length and level difference requirements that apply are summarized in Table 3-3.2 and are fully described as
follows (refer to Figure 3-3.1 and Figure 3-3.2):
Figure 3-3.1: The first connecting method