V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
67
7.2 Heating Capacity Tables
Table 2-7.6: KMF-80 DVN4 heating capacity
Combination (%)
(Capacity index)
Outdoor
temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
130%
-13.7
-15
6.13
1.65
6.11
1.69
6.09
1.76
6.09
1.81
6.06
1.86
6.04
1.88
-11.8
-13
6.22
1.68
6.20
1.72
6.18
1.80
6.18
1.84
6.15
1.89
6.15
1.91
-9.8
-11
6.31
1.70
6.29
1.75
6.27
1.82
6.27
1.86
6.27
1.91
6.25
1.91
-9.5
-10
6.36
1.73
6.34
1.77
6.34
1.84
6.31
1.89
6.31
1.94
6.29
1.94
-8.5
-9.1
6.41
1.75
6.38
1.79
6.36
1.86
6.36
1.91
6.36
1.96
6.34
1.96
-7
-7.6
6.47
1.75
6.45
1.82
6.45
1.88
6.43
1.93
6.43
1.98
6.41
1.99
-5
-5.6
6.98
1.83
6.95
1.87
6.93
1.94
6.93
2.00
6.91
2.00
6.88
2.01
-3
-3.7
7.07
1.88
7.04
1.90
7.02
1.97
7.02
2.03
7.00
2.02
6.98
2.04
0
-0.7
7.20
1.93
7.18
1.92
7.16
2.00
7.16
2.05
7.13
2.05
7.13
2.05
3
2.2
7.96
2.04
7.86
2.04
7.84
2.10
7.82
2.14
7.82
2.16
7.80
2.18
5
4.1
9.89
2.47
9.50
2.44
9.35
2.43
8.98
2.35
8.62
2.32
7.91
2.22
7
6
10.05
2.49
9.68
2.37
9.35
2.31
8.98
2.25
8.62
2.23
7.91
2.15
9
7.9
10.05
2.36
9.68
2.26
9.35
2.24
8.98
2.21
8.62
2.17
7.91
2.10
11
9.8
10.05
2.25
9.68
2.17
9.35
2.16
8.98
2.13
8.62
2.11
7.91
2.02
13
11.8
10.05
2.14
9.68
2.10
9.35
2.10
8.98
2.10
8.62
2.06
7.91
1.98
15
13.7
10.05
2.07
9.68
2.05
9.35
2.04
8.98
2.01
8.62
2.00
7.91
1.91
120%
-13.7
-15
6.13
1.80
6.10
1.85
6.08
1.90
6.08
1.95
6.08
1.99
6.06
2.01
-11.8
-13
6.22
1.83
6.19
1.87
6.18
1.93
6.17
1.97
6.17
2.01
6.15
2.03
-9.8
-11
6.31
1.84
6.29
1.88
6.29
1.95
6.26
1.99
6.26
2.04
6.24
2.07
-9.5
-10
6.35
1.86
6.33
1.90
6.33
1.96
6.31
2.01
6.31
2.05
6.29
2.09
-8.5
-9.1
6.40
1.88
6.38
1.92
6.38
1.98
6.35
2.03
6.35
2.07
6.33
2.09
-7
-7.6
6.47
1.91
6.45
1.96
6.45
2.01
6.42
2.05
6.42
2.09
6.40
2.12
-5
-5.6
6.97
1.93
6.95
1.97
6.93
2.03
6.93
2.07
6.93
2.12
6.90
2.15
-3
-3.7
7.06
1.96
7.04
2.00
7.02
2.05
7.02
2.10
6.99
2.14
6.99
2.17
0
-0.7
7.20
1.98
7.18
2.03
7.15
2.07
7.15
2.12
7.15
2.16
7.13
2.18
3
2.2
7.86
2.10
7.86
2.16
7.84
2.18
7.82
2.22
7.82
2.26
7.31
2.16
5
4.1
9.90
2.36
9.30
2.34
8.64
2.30
8.30
2.25
7.98
2.23
7.31
2.09
7
6
9.97
2.34
9.30
2.24
8.64
2.18
8.30
2.14
7.98
2.13
7.31
2.04
9
7.9
9.97
2.24
9.30
2.14
8.64
2.11
8.30
2.07
7.98
2.07
7.31
1.98
11
9.8
9.97
2.17
9.30
2.09
8.64
2.04
8.30
2.01
7.98
1.99
7.31
1.91
13
11.8
9.97
2.12
9.30
2.04
8.64
1.98
8.30
1.98
7.98
1.96
7.31
1.87
15
13.7
9.97
2.07
9.30
1.98
8.64
1.93
8.30
1.91
7.98
1.89
7.31
1.80
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.