Mini Amazon III Series
70
Table 2-7.6: KMF-80 DVN4 heating capacity (continued)
Combination (%)
(Capacity index)
Outdoor
temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
70%
-13.7
-15
5.81
2.10
5.42
1.93
5.05
1.90
4.85
1.86
4.66
1.83
4.27
1.76
-11.8
-13
5.81
2.05
5.42
1.89
5.05
1.87
4.85
1.83
4.66
1.80
4.27
1.73
-9.8
-11
5.81
2.02
5.42
1.86
5.05
1.83
4.85
1.79
4.66
1.77
4.27
1.69
-9.5
-10
5.81
2.00
5.42
1.84
5.05
1.79
4.85
1.75
4.66
1.72
4.27
1.64
-8.5
-9.1
5.81
1.98
5.42
1.83
5.05
1.73
4.85
1.69
4.66
1.66
4.27
1.59
-7
-7.6
5.81
1.95
5.42
1.80
5.05
1.65
4.85
1.61
4.66
1.59
4.27
1.51
-5
-5.6
5.81
1.89
5.42
1.75
5.05
1.61
4.85
1.57
4.66
1.54
4.27
1.47
-3
-3.7
5.81
1.79
5.42
1.69
5.05
1.56
4.85
1.52
4.66
1.50
4.27
1.42
0
-0.7
5.81
1.69
5.42
1.62
5.05
1.49
4.85
1.45
4.66
1.43
4.27
1.35
3
2.2
5.81
1.60
5.42
1.53
5.05
1.40
4.85
1.36
4.66
1.34
4.27
1.26
5
4.1
5.81
1.53
5.42
1.43
5.05
1.35
4.85
1.31
4.66
1.29
4.27
1.21
7
6
5.81
1.47
5.42
1.37
5.05
1.28
4.85
1.24
4.66
1.22
4.27
1.14
9
7.9
5.81
1.40
5.42
1.32
5.05
1.24
4.85
1.20
4.66
1.17
4.27
1.10
11
9.8
5.81
1.35
5.42
1.27
5.05
1.19
4.85
1.15
4.66
1.12
4.27
1.05
13
11.8
5.81
1.30
5.42
1.22
5.05
1.13
4.85
1.09
4.66
1.07
4.27
0.99
15
13.7
5.81
1.25
5.42
1.17
5.05
1.09
4.85
1.05
4.66
1.02
4.27
0.95
60%
-13.7
-15
4.98
1.86
4.66
1.77
4.32
1.70
4.16
1.63
3.98
1.55
3.66
1.45
-11.8
-13
4.98
1.80
4.66
1.70
4.32
1.63
4.16
1.57
3.98
1.48
3.66
1.39
-9.8
-11
4.98
1.74
4.66
1.64
4.32
1.55
4.16
1.50
3.98
1.42
3.66
1.34
-9.5
-10
4.98
1.68
4.66
1.57
4.32
1.49
4.16
1.44
3.98
1.36
3.66
1.27
-8.5
-9.1
4.98
1.61
4.66
1.52
4.32
1.43
4.16
1.38
3.98
1.29
3.66
1.19
-7
-7.6
4.98
1.55
4.66
1.45
4.32
1.38
4.16
1.33
3.98
1.24
3.66
1.14
-5
-5.6
4.98
1.49
4.66
1.40
4.32
1.31
4.16
1.27
3.98
1.19
3.66
1.09
-3
-3.7
4.98
1.44
4.66
1.34
4.32
1.25
4.16
1.22
3.98
1.14
3.66
1.05
0
-0.7
4.98
1.38
4.66
1.29
4.32
1.20
4.16
1.16
3.98
1.08
3.66
1.03
3
2.2
4.98
1.32
4.66
1.23
4.32
1.15
4.16
1.12
3.98
1.03
3.66
0.99
5
4.1
4.98
1.25
4.66
1.18
4.32
1.11
4.16
1.07
3.98
1.00
3.66
0.97
7
6
4.98
1.19
4.66
1.13
4.32
1.06
4.16
1.02
3.98
1.00
3.66
0.95
9
7.9
4.98
1.17
4.66
1.10
4.32
1.04
4.16
1.00
3.98
0.96
3.66
0.91
11
9.8
4.98
1.16
4.66
1.09
4.32
1.01
4.16
0.98
3.98
0.94
3.66
0.89
13
11.8
4.98
1.12
4.66
1.05
4.32
0.98
4.16
0.95
3.98
0.92
3.66
0.87
15
13.7
4.98
1.11
4.66
1.03
4.32
0.95
4.16
0.93
3.98
0.89
3.66
0.85
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.