V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
37
Table 2-7.2: KMF-100 DVN4 cooling capacity (continued)
Combination
(%) (Capacity
index)
Outdoor
temperature
(°C DB)
Indoor temperature(°C DB/WB)
DB:20.8,WB:14 DB:23.3,WB:16 DB:25.8,WB:18
DB:27,WB:19
DB:28.2,WB:20 DB:30.7,WB:22
DB:32,WB:24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
70%
-5
4.2
0.58
5.1
0.68
5.9
0.77
6.3
0.82
6.7
0.88
7.5
1.00
8.4
1.15
-2
4.2
0.58
5.1
0.68
5.9
0.77
6.3
0.84
6.7
0.89
7.5
1.02
8.4
1.17
0
4.2
0.58
5.1
0.69
5.9
0.79
6.3
0.85
6.7
0.91
7.5
1.04
8.4
1.18
2
4.2
0.59
5.1
0.69
5.9
0.80
6.3
0.87
6.7
0.92
7.5
1.06
8.4
1.20
4
4.2
0.60
5.1
0.71
5.9
0.82
6.3
0.88
6.7
0.94
7.5
1.08
8.4
1.23
6
4.2
0.61
5.1
0.72
5.9
0.84
6.3
0.91
6.7
0.97
7.5
1.10
8.4
1.26
8
4.2
0.62
5.1
0.74
5.9
0.86
6.3
0.93
6.7
0.99
7.5
1.13
8.4
1.28
10
4.2
0.63
5.1
0.75
5.9
0.88
6.3
0.95
6.7
1.01
7.5
1.15
8.4
1.30
12
4.2
0.64
5.1
0.76
5.9
0.90
6.3
0.96
6.7
1.03
7.5
1.17
8.4
1.32
14
4.2
0.65
5.1
0.78
5.9
0.91
6.3
0.98
6.7
1.05
7.5
1.20
8.4
1.35
16
4.2
0.67
5.1
0.79
5.9
0.93
6.3
1.00
6.7
1.07
7.5
1.22
8.4
1.37
18
4.2
0.68
5.1
0.81
5.9
0.95
6.3
1.02
6.7
1.09
7.5
1.24
8.4
1.40
20
4.2
0.69
5.1
0.82
5.9
0.96
6.3
1.04
6.7
1.11
7.5
1.27
8.4
1.44
21
4.2
0.69
5.1
0.83
5.9
0.97
6.3
1.05
6.7
1.12
7.5
1.28
8.4
1.49
23
4.2
0.70
5.1
0.84
5.9
0.99
6.3
1.08
6.7
1.18
7.5
1.38
8.4
1.59
25
4.2
0.72
5.1
0.88
5.9
1.06
6.3
1.16
6.7
1.26
7.5
1.47
8.4
1.70
27
4.2
0.76
5.1
0.94
5.9
1.13
6.3
1.23
6.7
1.34
7.5
1.57
8.4
1.82
29
4.2
0.81
5.1
0.99
5.9
1.20
6.3
1.31
6.7
1.43
7.5
1.68
8.4
1.95
31
4.2
0.85
5.1
1.05
5.9
1.28
6.3
1.39
6.7
1.52
7.5
1.79
8.4
2.07
33
4.2
0.91
5.1
1.12
5.9
1.36
6.3
1.48
6.7
1.62
7.5
1.90
8.4
2.21
35
4.2
0.96
5.1
1.19
5.9
1.44
6.3
1.58
6.7
1.72
7.5
2.03
8.4
2.36
37
4.2
1.01
5.1
1.26
5.9
1.53
6.3
1.68
6.7
1.83
7.5
2.16
8.4
2.51
39
4.2
1.07
5.1
1.33
5.9
1.63
6.3
1.78
6.7
1.95
7.5
2.29
8.4
2.68
41
4.2
1.12
5.1
1.38
5.9
1.67
6.3
1.84
6.7
2.01
7.5
2.39
8.4
2.79
43
4.2
1.21
5.1
1.48
5.9
1.74
6.3
1.94
6.7
2.06
7.5
2.48
8.4
2.88
45
4.2
1.24
5.1
1.51
5.9
1.78
6.3
1.97
6.7
2.17
7.5
2.61
8.4
2.99
48
4.2
1.26
5.1
1.52
5.9
1.80
6.3
2.01
6.7
2.23
7.5
2.73
8.4
3.06
50
4.2
1.28
5.0
1.53
5.8
1.81
6.2
2.01
6.6
2.24
7.4
2.74
8.3
3.08
52
4.1
1.29
5.0
1.54
5.8
1.81
6.1
2.02
6.5
2.25
7.3
2.75
8.1
3.09
54
4.1
1.29
4.9
1.55
5.6
1.83
6.0
2.03
6.4
2.26
7.2
2.77
8.0
3.11
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is above 43 degrees in cooling mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.
Содержание Mini Amazon III
Страница 140: ......