8 - ELECTRIC CONNECTIONS
pag. 29
8.4 SYSTEM ADDRESS AND NETWORK ADDRESS SETTING
/ '
After first powered on, please set the system address by remote
controller or wired controller, the address range is
0-63, the indoor
s
nit addresses of the same system can not be repeated.
0'
Display as the table 2, when there are different ENC1, the address
setting will be different (Fig.14).
Each independent control box needs to be set an address, this address is an actual address; when the capacity code
ENC1 is selected to be E-F, this indoor unit independent control box will produce
virtual address(es) with
corresponding quantity based on the set
actual address, and if an address has been an actual address or
virtual
address, then this address can not be the actual address or
virtual address of other indoor unit in the same system;
For example, if there are two independent control boxes in the same
system, one of the capacity code is E, the setting
actual address is
5, then according to the table 2 this control box will produce virtual
address as 6, and then the
actual address and the virtual address
m
f the other independent control box can not be any one of 5, 6.
The actual
address and the virtual address should less than or
equal to 63.
1'
The indoor unit quantity detected by outdoor unit will be the sum of
the actual address quantity and the virtual
address quantity, e.g.
when the capacity code of independent control box is E, the setting
actual address is 5, then it
will produce virtual address 6, and then
the indoor unit quantity detected by outdoor unit will be 2.
2'
The outdoor unit can not use auto addressing for to set the address
for the indoor unit without address; only the indoor
unit has address
then can the outdoor unit to be set auto addressing;
3'
When the independent control box system connects to the indoor
s
nit centralized controller, the actual address and
the virtualaddress
will be displayed on the centralized controller, e.g. when the then
the actual address 5 and virtual
address 6, will be displayed on the
centralized controller, that is to say, it equals to 2 indoor units, and
the states of 2
indoor units will be kept in the same;
4'
The network address is the same as the indoor unit address, no
need to setting separately.
SW4-2 ENC1
Corresponding Virtual Addresses
Qty of occupied
addresses
0
0~D
No virtual address
1
0
E-F
Actual a1
/
/
/
/
2
0
0-1
Actual a1
/
/
/
/
2
0
2-4
Actual a1
Actual a2
Actual a3
/
/
4
Table 5-2
0 1
3
4
5
67
89
AB
C
D
E F
fig. 15