Locate The Pipe

 

 

● 

Drill a hole in the wall (suitable just for the size of the wall conduit, 
90mm in general), then set on the fittings such as the wall conduit 
and its cover. 

 

● 

Bind the connecting pipe and the cables together tightly with 
binding tapes. Do not let air in, which will cause water leakage 
by condensation. 

9.3

 

Insulation

 

Be sure to with insulating materials cover all the exposed parts 
of the flare pipe joints and refrigerant pipe on the liquid-side and 
the gas-side. Ensure that there is no gap between them.

 

 

Incomplete insulation may cause water condensation.

 

 

● 

Pass the  bound connecting pipe through the wall conduit from 
outside.  Be careful of the pipe all location to do no damage to the 
tubing.

 

 

● 

Pass the  bound connecting pipe through the wall conduit from 
outside.  Be careful of the pipe all location to do no damage to the 
tubing.

 

 

Connect the pipes.

 

 

Then, open the stem of stop valves of the outdoor unit to make 
the refrigerant pipe connecting the indoor unit with the outdoor 
unit fluently flow.

 

 

Be sure of no leakage by checking it with leak detector or soap 
water.

 

 

Cover the joint of the connecting pipe to the indoor unit with the 
sound proof/insulating sheath (fittings), and bind it well with the 
tapes to prevent leakage.

 

 
 
 
 
 
 
 
 

Table.9-1

 

 
 

 

Fig.9-3

 

 

9.

 

REFRIGERANT PIPE CONNECTION 

9.1

 

Expel The Air

 

 

Flaring

 

 
 
 

Table.9-2

 

 

Fig.9-4

 

 

● 

Cut a pipe with a pipe cutter.

 

 

● 

Insert a flare nut into a pipe and flare the pipe.

 

 

lean crude burr

 

 

 

 

9.2

 

Check The Leakage

 

 

Fig.9-1

 

 

Fasten the nut

 

● 

Put the connecting tubing at the proper position, wrench  the 
nuts  with  hands  then  fasten  it  with  a  wrench.  (Refer  to 

Fig.9-4

 

Check all the joints with the leak detector or soap water. (See

 

Fig.9-6 

as a reference illustration)

 

 

A. Lo-stop valve 

B. Hi-stop valve

 

C,D. Joints of the connecting pipe to the indoor unit.

 

 

Fig.9-2

 

● 

Too large torque  will harm the bell  mouthing and too small 
will cause leakage. Please determine the torque according 
to Table.9-2.

 

 

The necessary filling amount of refrigerant

 

 

● 

Refrigerant  volume  to  be  added  is calculated  according  to 
outdoor unit installation manual. Be sure to add refrigerant 
measuring by a scale. L: The length of the pipe

 

 

● 

Please  record  the  quantity  added  and  store  it  carefully  for 
future maintenance.

 

 

Expel the air with a vacuum pump (Refer to 

Fig.9-4

) (Please 

refer to its manual for the way of using manifold valve)

 

 

● 

Loosen and remove the maintenance nuts of stop valves A 
and  B, and connect the charge hose of the manifold valve 
with  the  maintenance  terminator  of  stop  valve  A.  (Be  sure 
that stop valves A and B are both closed)

 

Check-point of indoor unit

 

D

 

C

 

B

 

A

 

Check-point of outdoor unit

 

90

 

90

+_4

 

A

 

4 5 _ +

2

 

 

Outside diameter

 

A(mm)

 

Max

 

Min

 

Φ6.4mm

 

8.7

 

8.3

 

Φ9.5mm

 

12.4

 

12.0

 

Φ12.7mm

 

15.8

 

15.4

 

Φ15.9mm

 

19.0

 

18.6

 

Φ19.1mm

 

23.3

 

22.9

 

 

Tubing size

 

Torque

 

Φ6.4mm

 

14.2~17.2N.m(144~176kgf.cm)

 

Φ9.5mm

 

32.7~39.9N.m(333~407kgf.cm)

 

Φ12.7mm

 

49.5~60.3N.m(504~616kgf.cm)

 

Φ15.9mm

 

61.8~75.4N.m(630~770kgf.cm)

 

Φ19.1mm

 

97.2~118.6N.m(990~1210kgf.cm)

 

 

Содержание KPDHF-71 DN3.0

Страница 1: ...0 DN3 0 KPDHF 160 DN3 0 KPDHF 200 DN3 0 KPDHF 250 DN3 0 KPDHF 280 DN3 0 The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before...

Страница 2: ...MD14I 041FW DZ2 16100101A01132...

Страница 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Страница 4: ...ive and negative poles are in right positions when loading batteries 4 INDOOR UNIT INSTALLATION Installing 10 Hanging Screw Bolts 4 Bolts Please refer to the following figure for the distance measurem...

Страница 5: ...eel refer to Fig 4 4 Overhanging the indoor unit Fig 4 4 Fig 4 7 Overhang the indoor unit onto the hanging screw bolts with block Position the indoor unit in a flat level by using the level indicator...

Страница 6: ...ONNECTION SAFETY DRAIN CONNECTING PIPE AIR OUTLET 255 33 65 722 65 Fig 4 9 14 16KW 135 930 88 Unit mm PLASTIC COVER 68 24 46 ELECTRICAL CONTROL BOX 4 12 25OBLONGSUSPENTIONBOLTHOLES AIR INTAKE CONNECTI...

Страница 7: ...w as Fig 4 11 SafetyDrainTray Fig 4 12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arr...

Страница 8: ...all 4 bolts from reinforced panel and take off the panel 3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fanassembly 4 Refer to Fig 4 1...

Страница 9: ...11 screw from fixed Safety Drain Tray and then take off the tray as figure showed inFig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re...

Страница 10: ...m fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightl...

Страница 11: ...nnection 9 52 3 8 Refrigerant pipe flared connection 16 5 8 Air intake duct flange 1270 Connecting point of drain pipe 43 125 100 Air intake 936 200 Fig 4 19 The method of installation adopt following...

Страница 12: ...onfirm that there is enough room for installation and mainte nance Maintenance roomage Maintenance roomage motor assembly bottom cover plate screw Confirm the minimum drain tilt is 1 100 or more check...

Страница 13: ...ut dust filter dust adherent on the air heat exchanger may cause failure and water leak Key points of duct connection Canvas tie in Canvas tie in Fig 7 1 Other assemblies should be prepared on spot ex...

Страница 14: ...12 9KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 7 Fig 7 5 11 2KW model fan curve the static pressure refer to Table 12 2 Middle fan speed Fig 7 6 Hig...

Страница 15: ...installation manual 13 Middle fan speed 14KW model fan curve the static pressure refer to Table 12 2 High fan speed Low fan speed Fig 7 9 Fig 7 10 Middle fan speed Fig 7 11 Fig 7 12...

Страница 16: ...installation manual 14 Low fan speed Middle fan speed Fig 7 13 16KW model fan curve the static pressure refer to Table 12 2 Low fan speed Fig 7 15 High fan speed Fig 7 16 Fig 7 14...

Страница 17: ...20KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 19 Middle fan speed Fig 7 17 25KW 28KW model fan curve the static pressure refer to Table 12 2 High fan...

Страница 18: ...1 Hang the outside frame on the main body with face down 4 places at 4 corners Hang the belt on the hook of the main body Low fan speed Fig 7 22 The signal wire of the remote control receiver must be...

Страница 19: ...urities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connectingth...

Страница 20: ...pipe cutter Insert a flare nut into a pipe and flare the pipe lean crude burr 9 2 Check The Leakage Fig 9 1 Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands...

Страница 21: ...l should be more than 50mm and the drain pipe cannot put in water If the drain water was discharged to ditch directly the drain pipe must be upward bent into a U type water seal to avoid odor into the...

Страница 22: ...itioners The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 3 and Fig 11 4 is the wiring for 200T1 250T1 and 280T1 indoor unit Table 11 1 Capacity KW 71 80 90 112 140 160 200 250 280 Power...

Страница 23: ...DOOR COMM BUS POWER INPUT Y G For 200 250 280 models TA A T1 A T2 A T2B A XP4 XS4 XP5 XS5 OLD DISPLAY BOARD WIRE CONTROLLER DC FAN TA B T1 B T2 B T2B B WHITE BLACK CN23 CN24 CN25 CN26 CN15 CN10 CN16 W...

Страница 24: ...ll distribute different addresses for indoor units automatically When V4 outdoor unit set the code to be found address non automatically all the indoor units must set the system addresses by remote co...

Страница 25: ...ing SW6 ON 1234 l reserved For B SYSTEM SW 1 Difinition SW 2 Difinition SW3 ON 1 2 l 00 means the time ofstopping TERMAL fan is 4 mintues SW3 ON 1 2 l 01 means the time ofstopping TERMAL fan is 8 mint...

Страница 26: ...rtfunction J2 l r eserve d 0 1 Definition ON l means 0 ON l means 1 Please adjust the code ENC1 to the suitable position both system A and B should be adjusted for 200T1 250T1 and 280T1 indoor unit Th...

Страница 27: ...rement install the remotecontroller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remotecontro...

Страница 28: ......

Отзывы: