SW 5  Difinition

 

 

 

 

 

 

SW6 Difinition

 

 

 

 

 

 

SW7 Difinition

 

 

 

● 

To prevent collapsing of deforming, please bend the pipe at its 
biggest radius. 

 

● 

Use bender to get a small radius pipes. 

Use the market brass pipe.

 

Be sure to use the same insulating materials when you buy the 
brass pipe. (More than 9mm thick)

 

 

For  200T1  unit,  a  mainboard  in  the  electric  control  should  set 
the  code  ENC1 to  B; the  other  one should  set the  code  ENC1 
to 8;

 

 

For  250T1  unit,  a  mainboard  in  the  electric  control  should  set 
the  code  ENC1 to  C; the  other  one  should set the code  ENC1 
to 9;

 

 

For  280T1  unit,  a  mainboard  in  the  electric  control  should  set 
the  code  ENC1 to  D; the  other  one should set the code  ENC1 
to 9;

 

When using central controller to control the indoor unit,

 

please  pay  attention  to  the  address  setting,  as  the  220T1, 
250T1  and  280T1  units  have  two  or  more  mainboards.  We 
suggest setting the neighbor address for the mainboards

 

in  the  same  indoor  unit.  When  using  a  central  controller  for 
controlling, mainboards in the same unit must be opened

 

and  closed  at  the  same  time,  for  avoiding  the  unexpected 
incident.

 

 

 

 

 

 

 

 

 

For both T1

 

 

J1, J2 Definition

 

J1 

 

l

 

without jumper "J1" fo r 
auto restart function

 

J1 

 

 

l

 

with jumper "J1" for 
non-auto restart function

 

J2 

 

 

 

l

 

r eserve d

 

 

0/1 Definition

 

 

 

ON

 

 

l

 

means 0

 

 

ON

 

 

l

 

means 1

 

 
 
 
 
 
 
 

Please adjust the code ENC1 to the suitable position (both 
system A and B should be adjusted for 200T1, 250T1 and 
280T1 indoor unit).

 

 

●  Then expose the pipe (cover it with tapes after bending). 

13.

 

TROUBLE SHOOTING 

Table.13-1

 

 

NO.

 

Error code

 

Indication

 

 

1

 

Timer LED and run LED 
flash together, or show 
"FE"

 

No address when first time 
power on

 

 

2

 

Defrost LED flash 
or show "E0"

 

 

Mode conflict

 

 

3

 

Timer LED flash 
or show "E1"

 

Communication error between 
indoor and outdoor unit

 

 

4

 

Run LED flash 
or show "E2"

 

 

Temp.sensor (T1) error

 

 

5

 

Run LED flash 
or show "E3"

 

 

Temp.sensor (T2) error

 

 

6

 

Run LED flash 
or show "E4"

 

 

Temp.sensor (T2B) error

 

 

7

 

 

Timer LED flash slowly 
or show "E6"

 

 

DC FAN error

 

 

8

 

Defrost LED flash slowly 
or show "E7"

 

 

EEPROM error

 

 

9

 

Alarm LED flash slowly 
or show "Ed"

 

 

Outdoor unit error

 

 

10

 

Alarm LED flash 
or show "EE"

 

 

Water level alarm

 

 

SW5

 

ON

 

1 2

 

l

 

00 means temp.compensation 

value is 6

℃ 

under heat mode

 

SW5

 

ON

 

1 2

 

l

 

01 means temp.compensation 

value is 2

℃ 

under heat mode

 

SW5

 

ON

 

1 2

 

l

 

10 means temp.compensation 

value is 4

℃ 

under heat mode

 

SW5

 

ON

 

1 2

 

l

 

11 means temp.compensation 

value is 8

℃ 

under heat mode

 

 

SW6

 

ON

 

1 2 3

 

l

 

1 means old display panel

 

l

 

0 means new display panel

 

SW6

 

ON

 

1 2 3

 

l

 

1 means auto air blow under 

auto  m ode

 

l

 

0 means auto air blow under

 

non-auto mode

 

SW6

 

ON

 

1 2 3

 

 

l

 

reserved

 

 

SW7

 

ON

 

1 2

 

l

 

standard 

configuration

 

SW7

 

ON

 

1 2

 

l

 

last unit of 

the network

 

 

Содержание KPDHF-71 DN3.0

Страница 1: ...0 DN3 0 KPDHF 160 DN3 0 KPDHF 200 DN3 0 KPDHF 250 DN3 0 KPDHF 280 DN3 0 The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before...

Страница 2: ...MD14I 041FW DZ2 16100101A01132...

Страница 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Страница 4: ...ive and negative poles are in right positions when loading batteries 4 INDOOR UNIT INSTALLATION Installing 10 Hanging Screw Bolts 4 Bolts Please refer to the following figure for the distance measurem...

Страница 5: ...eel refer to Fig 4 4 Overhanging the indoor unit Fig 4 4 Fig 4 7 Overhang the indoor unit onto the hanging screw bolts with block Position the indoor unit in a flat level by using the level indicator...

Страница 6: ...ONNECTION SAFETY DRAIN CONNECTING PIPE AIR OUTLET 255 33 65 722 65 Fig 4 9 14 16KW 135 930 88 Unit mm PLASTIC COVER 68 24 46 ELECTRICAL CONTROL BOX 4 12 25OBLONGSUSPENTIONBOLTHOLES AIR INTAKE CONNECTI...

Страница 7: ...w as Fig 4 11 SafetyDrainTray Fig 4 12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arr...

Страница 8: ...all 4 bolts from reinforced panel and take off the panel 3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fanassembly 4 Refer to Fig 4 1...

Страница 9: ...11 screw from fixed Safety Drain Tray and then take off the tray as figure showed inFig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re...

Страница 10: ...m fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightl...

Страница 11: ...nnection 9 52 3 8 Refrigerant pipe flared connection 16 5 8 Air intake duct flange 1270 Connecting point of drain pipe 43 125 100 Air intake 936 200 Fig 4 19 The method of installation adopt following...

Страница 12: ...onfirm that there is enough room for installation and mainte nance Maintenance roomage Maintenance roomage motor assembly bottom cover plate screw Confirm the minimum drain tilt is 1 100 or more check...

Страница 13: ...ut dust filter dust adherent on the air heat exchanger may cause failure and water leak Key points of duct connection Canvas tie in Canvas tie in Fig 7 1 Other assemblies should be prepared on spot ex...

Страница 14: ...12 9KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 7 Fig 7 5 11 2KW model fan curve the static pressure refer to Table 12 2 Middle fan speed Fig 7 6 Hig...

Страница 15: ...installation manual 13 Middle fan speed 14KW model fan curve the static pressure refer to Table 12 2 High fan speed Low fan speed Fig 7 9 Fig 7 10 Middle fan speed Fig 7 11 Fig 7 12...

Страница 16: ...installation manual 14 Low fan speed Middle fan speed Fig 7 13 16KW model fan curve the static pressure refer to Table 12 2 Low fan speed Fig 7 15 High fan speed Fig 7 16 Fig 7 14...

Страница 17: ...20KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 19 Middle fan speed Fig 7 17 25KW 28KW model fan curve the static pressure refer to Table 12 2 High fan...

Страница 18: ...1 Hang the outside frame on the main body with face down 4 places at 4 corners Hang the belt on the hook of the main body Low fan speed Fig 7 22 The signal wire of the remote control receiver must be...

Страница 19: ...urities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connectingth...

Страница 20: ...pipe cutter Insert a flare nut into a pipe and flare the pipe lean crude burr 9 2 Check The Leakage Fig 9 1 Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands...

Страница 21: ...l should be more than 50mm and the drain pipe cannot put in water If the drain water was discharged to ditch directly the drain pipe must be upward bent into a U type water seal to avoid odor into the...

Страница 22: ...itioners The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 3 and Fig 11 4 is the wiring for 200T1 250T1 and 280T1 indoor unit Table 11 1 Capacity KW 71 80 90 112 140 160 200 250 280 Power...

Страница 23: ...DOOR COMM BUS POWER INPUT Y G For 200 250 280 models TA A T1 A T2 A T2B A XP4 XS4 XP5 XS5 OLD DISPLAY BOARD WIRE CONTROLLER DC FAN TA B T1 B T2 B T2B B WHITE BLACK CN23 CN24 CN25 CN26 CN15 CN10 CN16 W...

Страница 24: ...ll distribute different addresses for indoor units automatically When V4 outdoor unit set the code to be found address non automatically all the indoor units must set the system addresses by remote co...

Страница 25: ...ing SW6 ON 1234 l reserved For B SYSTEM SW 1 Difinition SW 2 Difinition SW3 ON 1 2 l 00 means the time ofstopping TERMAL fan is 4 mintues SW3 ON 1 2 l 01 means the time ofstopping TERMAL fan is 8 mint...

Страница 26: ...rtfunction J2 l r eserve d 0 1 Definition ON l means 0 ON l means 1 Please adjust the code ENC1 to the suitable position both system A and B should be adjusted for 200T1 250T1 and 280T1 indoor unit Th...

Страница 27: ...rement install the remotecontroller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remotecontro...

Страница 28: ......

Отзывы: