installation manual

 

20

 

 

11.

 

WIRING 

Attaching wiring

 

 

● 

The air conditioner should use separate power supply with rated 
voltage. 

 

● 

The external power supply to the air conditioner should  have 
ground wiring, which is linked to the ground wiring of the indoor 
and outdoor unit. 

 

● 

The wiring work should be done by qualified persons according 
to circuit drawing. 

 

● 

A leakage protector should be installed according to the National 
Standard concerning electrical appliance. 

 

● 

Be sure to locate the power wiring and the signal wring well to 
avoid cross-disturbance and their contact with connecting pipe 
or stop value body. 

 

● 

The wiring attached to this air conditioner is 10m long.  Be sure 
to prolong it with wiring of the same type and proper length if 
necessary. Generally, do not twist two wiring together unless 
the joint is soldered well and covered with insulator tape. 

 

● 

Do not turn on the power until you have checked carefully after 
wiring. 

The Specification of Power

 

 

Fig.11-2

 

 

 

The reserved function is indicated in broken line table, users can 
select it when necessary.

 

 

 

 

 

Terminal board diagram

 

 

Please refer to the indoor unit wiring diagram for the detailed 
wiring. In accord with the communication wiring, terminal board 
wiring is different according to the horsepower of air-conditioners. 
The wiring of 71T1 to 160T1 indoor unit, please refer to Fig.11-3, 
and Fig.11-4 is the wiring for 200T1, 250T1 and 280T1 indoor unit.

 

Table.11-1

 

 

Capacity(KW)

 

71/80/90/112/140/160

 

200/250/280

 

 

Power

 

Phase

 

1-Phase

 

Frequency and volt

 

220-240V

50/60Hz

 

Circuit breaker/fuse (A)

 

10/10

 

16/10

 

Indoor unit power wiring (mm

2

)

 

2.5(<20 m)-4.0(<50 m)

 

Indoor/outdoor 
connecting 
wiring(mm

2

)

 

Ground wiring

 

2.0

 

Weak electric signal

 

0.75(<1200 m)

 

 

 

 

A disconnection device having an air gap contact separation in 
all active conductors should be incorporated in the fixed wiring 
according to the National Wiring Regulation.

 

Communication Wiring Chart

 

Communication wiring will be different according to the horse- 
power of air-conditioners. The wiring of 71T1 to 160T1 indoor 
unit, please refer to Fig.11-1, and Fig.11-2 is the communication 
wiring for 200T1, 250T1 and 280T1 indoor unit.

 

 

 

 

The air-conditioners can connect with Central Control Monitor 
(CCM).  Before  operation,  please  wiring  correctly  and  set 
system address and network address of indoor units.

 

 

 

 

 

Please use 3-core shielding wire, and ground the shielding layer.

 

Fig.11-3

 

 
 
 

 

INDOOR UNIT

 

YELLOW/GREEN

 

 

XT2

 

 

XT3

 

L  N

 

 

 
 

 

TO CCM 

COMM.BUS

 

 
 
 

TO INDOOR&OUTDOOR 

COMM.BUS

 

 
 

 

TO CCM 

COMM.BUS

 

 
 

 

TO INDOOR&OUTDOOR 

COMM.BUS

 

 

TO INDOOR POWER SUPPLY

 

220-240V~ 50/60Hz

 

TO NEXT INDOOR UNIT

 

 

Please use 3-core shielding wire, and ground the shielding layer.

 

 

 

Fig.11-4

 

 
 
 
 

 

Fig.11-1

 

CAUTION

 

  

NOTE 

 

OUTDOOR UNIT

 

 

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

INDOOR UNIT

 

 

 

     

  

 

 

 

 

 

 

  

 

CAUTION

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

OUTDOOR UNIT

 

 

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

    

 

  

 

    

  

 

 

 

 

 

 

 

 

Содержание KPDHF-71 DN3.0

Страница 1: ...0 DN3 0 KPDHF 160 DN3 0 KPDHF 200 DN3 0 KPDHF 250 DN3 0 KPDHF 280 DN3 0 The Digital Scroll and DC AC Inverter share the same indoor units Thank you very much for purchasing our air conditioner Before...

Страница 2: ...MD14I 041FW DZ2 16100101A01132...

Страница 3: ...nce and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do n...

Страница 4: ...ive and negative poles are in right positions when loading batteries 4 INDOOR UNIT INSTALLATION Installing 10 Hanging Screw Bolts 4 Bolts Please refer to the following figure for the distance measurem...

Страница 5: ...eel refer to Fig 4 4 Overhanging the indoor unit Fig 4 4 Fig 4 7 Overhang the indoor unit onto the hanging screw bolts with block Position the indoor unit in a flat level by using the level indicator...

Страница 6: ...ONNECTION SAFETY DRAIN CONNECTING PIPE AIR OUTLET 255 33 65 722 65 Fig 4 9 14 16KW 135 930 88 Unit mm PLASTIC COVER 68 24 46 ELECTRICAL CONTROL BOX 4 12 25OBLONGSUSPENTIONBOLTHOLES AIR INTAKE CONNECTI...

Страница 7: ...w as Fig 4 11 SafetyDrainTray Fig 4 12 2 Remove the all 11 screw from fixed Safety Drain Tray and then take off the tray as figure showed in Fig 5 11 3 Take off the tray along the direction of the arr...

Страница 8: ...all 4 bolts from reinforced panel and take off the panel 3 Refer to Fig 4 13 remove all 4 bolts from fan assembly see Fig 4 14 according to which orders to take off the fanassembly 4 Refer to Fig 4 1...

Страница 9: ...11 screw from fixed Safety Drain Tray and then take off the tray as figure showed inFig 4 16 3 Take off the tray along the direction of the arrow show in Fig 4 16 4 Clean the tray and evaporator 5 Re...

Страница 10: ...m fan assembly see Fig 4 18 according to which orders to take off the fan assembly 3 Refer to Fig 4 18 horizontal pushing the fan assembly until it cannot not move any further and then lift up slightl...

Страница 11: ...nnection 9 52 3 8 Refrigerant pipe flared connection 16 5 8 Air intake duct flange 1270 Connecting point of drain pipe 43 125 100 Air intake 936 200 Fig 4 19 The method of installation adopt following...

Страница 12: ...onfirm that there is enough room for installation and mainte nance Maintenance roomage Maintenance roomage motor assembly bottom cover plate screw Confirm the minimum drain tilt is 1 100 or more check...

Страница 13: ...ut dust filter dust adherent on the air heat exchanger may cause failure and water leak Key points of duct connection Canvas tie in Canvas tie in Fig 7 1 Other assemblies should be prepared on spot ex...

Страница 14: ...12 9KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 7 Fig 7 5 11 2KW model fan curve the static pressure refer to Table 12 2 Middle fan speed Fig 7 6 Hig...

Страница 15: ...installation manual 13 Middle fan speed 14KW model fan curve the static pressure refer to Table 12 2 High fan speed Low fan speed Fig 7 9 Fig 7 10 Middle fan speed Fig 7 11 Fig 7 12...

Страница 16: ...installation manual 14 Low fan speed Middle fan speed Fig 7 13 16KW model fan curve the static pressure refer to Table 12 2 Low fan speed Fig 7 15 High fan speed Fig 7 16 Fig 7 14...

Страница 17: ...20KW model fan curve the static pressure refer to Table 12 2 Low fan speed High fan speed Fig 7 19 Middle fan speed Fig 7 17 25KW 28KW model fan curve the static pressure refer to Table 12 2 High fan...

Страница 18: ...1 Hang the outside frame on the main body with face down 4 places at 4 corners Hang the belt on the hook of the main body Low fan speed Fig 7 22 The signal wire of the remote control receiver must be...

Страница 19: ...urities may enter the pipe system and may cause malfunction later So please expel the air out of the pipe with refrigerant before connection Expel the air refer to the Expel The Air after connectingth...

Страница 20: ...pipe cutter Insert a flare nut into a pipe and flare the pipe lean crude burr 9 2 Check The Leakage Fig 9 1 Fasten the nut Put the connecting tubing at the proper position wrench the nuts with hands...

Страница 21: ...l should be more than 50mm and the drain pipe cannot put in water If the drain water was discharged to ditch directly the drain pipe must be upward bent into a U type water seal to avoid odor into the...

Страница 22: ...itioners The wiring of 71T1 to 160T1 indoor unit please refer to Fig 11 3 and Fig 11 4 is the wiring for 200T1 250T1 and 280T1 indoor unit Table 11 1 Capacity KW 71 80 90 112 140 160 200 250 280 Power...

Страница 23: ...DOOR COMM BUS POWER INPUT Y G For 200 250 280 models TA A T1 A T2 A T2B A XP4 XS4 XP5 XS5 OLD DISPLAY BOARD WIRE CONTROLLER DC FAN TA B T1 B T2 B T2B B WHITE BLACK CN23 CN24 CN25 CN26 CN15 CN10 CN16 W...

Страница 24: ...ll distribute different addresses for indoor units automatically When V4 outdoor unit set the code to be found address non automatically all the indoor units must set the system addresses by remote co...

Страница 25: ...ing SW6 ON 1234 l reserved For B SYSTEM SW 1 Difinition SW 2 Difinition SW3 ON 1 2 l 00 means the time ofstopping TERMAL fan is 4 mintues SW3 ON 1 2 l 01 means the time ofstopping TERMAL fan is 8 mint...

Страница 26: ...rtfunction J2 l r eserve d 0 1 Definition ON l means 0 ON l means 1 Please adjust the code ENC1 to the suitable position both system A and B should be adjusted for 200T1 250T1 and 280T1 indoor unit Th...

Страница 27: ...rement install the remotecontroller frame where the remote controller s signal can reach the indoor unit smoothly Test operation Set the air conditioner under the mode of COOLING with the remotecontro...

Страница 28: ......

Отзывы: