15
● Do not directly connect the appliance to the main
power supply. Install the main power supply
breaker.
● If the supply cord is damaged, it must be replaced
by the manufacturer or its service agent or a
similarly qualified person in order to avoid creating
a hazard.
● An all-pole disconnection switch which has a
contact separation of at least 3 mm in all poles
shall be connected using fixed wiring.
● The appliance shall be installed in accordance
with national wiring regulations.
● The temperature of the refrigerant circuit will be
high. Please keep the interconnection cable away
from the copper tube.
● An all-pole disconnection device which has at
least 3 mm of separation distance in all poles and
a residual current device (RCD) with a rating of
above 10 mA shall be incorporated in the fixed
wiring in accordance with national requirements.
● The power cable model is H05RN-R/H07RN-F or above.
● Ask an authorized dealer or qualified installation
professional to install or maintain the air
conditioner.
● Incorrect installation may result in water leakage,
electric shock or fire.
● Turn off the main power supply breaker before
attempting any electrical work.
● Make sure all power breakers are off. Failure to do
so may cause electric shock.
● Connect the connecting cable correctly.
● If the connecting cable is connected incorrectly,
electric parts may become damaged.
● When relocating the air conditioner that is to be
installed, be very careful to prevent the entry of
any gaseous matter other than the specified
refrigerant into the refrigeration cycle.
● If air or any other gas is mixed into the refrigerant,
the gas pressure in the refrigeration cycle can
become abnormally high and it may cause pipes
to burst, leading to injury.
● Do not modify this unit by removing any of the
safety guards or by by-passing any of the safety
interlock switches.
● Exposure of the unit to water or other moisture
before installation may cause a short-circuiting of
electrical parts.
● Do not store the unit in a wet basement or expose
it to rain or water.
● After unpacking the unit, examine it carefully to
see if there is possible damage.
● Do not install the unit in a place that might
increase the vibration of the unit.
● To avoid personal injury (with sharp edges), be
careful when handling parts.
● Perform installation work properly according to
the Installation Manual.
● Incorrect installation may result in water leakage,
electric shock or fire.
● When the air conditioner is installed in a small
room, take appropriate measures to ensure that
the concentration of refrigerant leakage occurring
in the room does not exceed the critical level.
● Install the air conditioner securely in a location
where the base can adequately sustain the
weight.
● Perform the specified installation work to guard
against earthquakes.
● If the air conditioner is not installed properly, the
unit could fall and cause an accident.
Warning
● If refrigerant gas has leaked during installation,
ventilate the room immediately.
● If the leaked refrigerant gas comes into contact
with fire, noxious gas may be generated.
● After the installation, confirm that refrigerant gas
does not leak.
● If refrigerant gas leaks into the room and flows
near a source of flame, such as a cooking range,
noxious gas might be generated.
● Electrical work must be performed by a qualified
electrician in accordance with the Installation
Manual. Make sure the air conditioner uses a
dedicated power supply.
● An insufficient power supply capacity or
inappropriate installation may cause fire.
● Use the specified cables for wiring to connect
the terminals securely, and to prevent external
forces applied to the terminals from affecting the
terminals.
● Be sure to provide grounding.
● Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
cables.
● Conform to the regulations of the local electric
company when wiring the power supply.
● Improper grounding may cause electric shock.
● Do not install the air conditioner in a location
subject to a risk of exposure to combustible gas.
● If combustible gas leaks and stays around the
unit, a fire may occur.
Required tools for installation work
1) Phillips screw driver
2) Hole core drill (65 mm)
3) Spanner
4) Pipe cutter
5) Knife
6) Reamer
7) Gas leak detector
8) Tape measure
9) Thermometer
10) Mega-tester
11) Electro circuit tester
12) Hexagonal wrench
13) Flaring tool
14) Pipe bender
15) Level vial
16) Metal saw
17) Gauge manifold (Charge hose: R32 special requirement)
18) Vacuum pump (Charge hose: R32 special requirement)
19) Torque wrench
1/4 (17 mm) 16 N·m (1.6 kgf·m)
13/8 (22 mm) 42 N·m (4.2 kgf·m)
11/2 (26 mm) 55 N·m (5.5 kgf·m)
15/8 (15.9 mm) 120 N·m (12.0 kgf·m)
20) Copper pipe gauge adjusting projection margin
21) Vacuum pump adapter
The equipment complies with IEC 61000-3-12.