55
MDV-V140WHN8(At) Q4
Heating mode:
Information requirements for heat pumps
Model(s): MDV-V140WHN8(At)
Test matching indoor units form,no-duct: 2x MIH2x MIH45Q4N18
Outdoor side heat exchanger of air conditioner: air
Indoor side heat exchanger of air conditioner: air
If the heater is equipped with a supplementary heater: no
Driver of compressor: electric motor
Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons are
optional.
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Rated heating capacity
P
rated,h
14.00
kW
Seasonal space heating
energy efficiency
η
s,h
181.0
%
Declared heating capacity for part load at indoor
temperature 20°C and outdoor temperatures T
j
Declared coefficient of performance or gas utilisation
efficiency/auxiliary energy factor for part load at given
outdoor temperatures T
j
T
j
=-7°C
P
dh
8.85
kW
T
j
=-7°C
COP
d
2.90
--
T
j
=+2°C
P
dh
5.39
kW
T
j
=+2°C
COP
d
4.45
--
T
j
=+7°C
P
dh
3.46
kW
T
j
=+7°C
COP
d
6.00
--
T
j
=+12°C
P
dh
1.54
kW
T
j
=+12°C
COP
d
7.50
--
T
biv
=bivalent
temperature
P
dh
10.00
kW
T
biv
=bivalent temperature
COP
d
2.30
--
T
OL
=operation
temperature
P
dh
10.00
kW
T
OL
=operation temperature
COP
d
2.30
--
Bivalent temperature
T
biv
-10
°C
Degradation co-
efficient for heat
pumps(**)
C
dh
0.25
--
Power consumption in modes other than "active mode"
Supplementary heater
Off mode
P
OFF
0.028
kW
Back-up heating capacity(*)
elbu
0
kW
Thermosat-off mode
P
TO
0.028
kW
Type of energy input
Crankcase heater mode
P
CK
0.002
kW
Standby mode
P
SB
0.028
kW
Other items
Capacity control
variable
For air-to-air heat pump: air
flow rate, outdoor measured
--
5000
m³/h
Sound power level,
outdoor
L
WA
71
dB
GWP of the refrigerant
675
kg CO
2 eq
(100years)
Contact details
(*)
(**)If C
dh
is not determined by measurement, then the default degradation coefficient of heat pumps shall be 0.25.
Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of
performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Содержание KMF-80 DVR5
Страница 67: ...16127000005207...
Страница 68: ......