35
▪ Communication Wiring Diagram (when ODU is connected with VRF IDU and hydraulic module)
Figure 16-6
Communication wire
Power cable
···
L2
Power distribution
cabinet
Power distribution
cabinet
Circuit breaker
N L
IDU n
·
···
·
IDU 1
P Q E
P Q E
P Q E
L N GND
Fuse
Fuse
L1
L
L
N
N
L
L
N
IDU 2
P Q E
Fuse
Fuse
F
……
Resistor
L
L
N
L
L
N
N
N
P Q E
Fuse
F
Ln
……
Lt
Hydraulic module
ODU
● L1 + L2 + Ln + Lt ≤ 1,200 m, communication wire 3 × 0.75 mm².
● After the last IDU, the communication wire should not route back the ODU to form a closed loop.
● Connect a 120ohm resistor between terminals P and Q of the last IDU.
● All communication wires between IDU and ODU must be in serial connection. Shielded cables shall be used. Connect
the shielding nets at both ends of the shielded cable to the sheet metal " " of the electrical control box.
● Applicable standards: EN 55014-1 and EN 55014-2.
Caution
●
Communication Wiring Diagram (when ODU is only connected with hydraulic module)
Figure 16-7
Communication wire
Power cable
ODU
Circuit breaker
N L
P Q E
L N GND
Fuse
L1
L
L
N
L
L
N
N
N
P Q E
Fuse
F
Resistor
Hydraulic module
● L1 ≤ 1,200 m, communication wiring 3 × 0.75 mm².
● After the last IDU, the communication wire should not route back the ODU to form a closed loop.
● Connect a 120ohm resistor between terminals P and Q of the last IDU.
● All communication wires between IDU and ODU must be in serial connection. Shielded cables shall be used. Connect
the shielding nets at both ends of the shielded cable to the sheet metal " "of the electrical control box.
● Applicable standards: EN 55014-1 and EN 55014-2.
Caution
Содержание KMF-80 DVR5
Страница 67: ...16127000005207...