60
Fan Types
Axial fan
Directive (or Standard) for Regulation
ErP Directive 2009/125/EC
COMMISSION REGULATION (EU) No 327/2011
Model Name
ZKSN-200-10-3L+ZL-580*200*12-3N
Rev.
Prepare by
Specified Information of Fan:
No.
Information Item
Comment
1
η
target
=
30.26%
2
Overall efficiency (η
e
) =
33.39%
3
Pass or not (Criteria: η
e
≧
η
target
)
Pass
4
Measurement category (A-D)
A
5
Efficiency category (static or total)
Static
6
Efficiency grade at optimum energy efficiency point
N =42.1
7
VSD is integrated within the fan
YES
8
Year of Manufacture
Ref. to the Unit Nameplate
9
Manufacturer’s name and place of manufacture
Ref. to the Unit Nameplate
10.1
Rated motor power input(s) (kW), at optimum energy efficiency
0.288
10.2
Flow rate(s) at optimum energy efficiency (m
3
/h)
5615
10.3
Pressure(s) at optimum energy efficiency (Pa)
60
11
Rotations per minute (R.P.M) at the optimum energy efficiency
point
900r/min
12
Specific ratio
1.001
13
Information relevant for facilitating disassembly, recycling or dispos-
al at end-of-life
all materials can be recycled
14
Information relevant to minimize impact on the environment and
ensure optimal life expectancy as regards installation, use and
maintenance of the fan
For installation, the clearance of 500 mm
shall be kept from inlet
15
Description of additional items used when determining the fan ener-
gy efficiency, such as ducts, that are not described in the measure-
ment category and not supplied with the fan.
Measurement category A, fan is free inlet
and outlet conditions
16
Motor manufacturer
GUANGDONG WELLING MOTOR
MANUFACTURING CO.,LTD.
Содержание KMF-80 DVR5