background image

28

14.3.3 Gas Tightness Test

To  prevent  faults  caused  by  refrigerant  leakage,  a  gas 

tightness  test  should  be  performed  before  system 

commissioning.

●  Only  dry  nitrogen  should  be  used  for  gas 

tightness  testing.  Oxygen,  air,  flammable 

gases and toxic gases must not be used for 

gas tightness testing. Use of such gases may 

result in fire or explosion.

●  Make sure that all the outdoor unit stop valves 

are firmly closed.

●  Make sure all piping connections are complete 

before the tightness test begins.

 CAUTION

The gas tightness test procedure is as follows:
1.Charge  the  indoor  piping  with  nitrogen  at  0.3Mpa 

through  the  needle  valves  on  the  liquid  and  gas  stop 

valves and leave for at least 3 minutes (do not open the 

liquid or gas stop valves). Observe the pressure gauge to 

check for large leakages. If there is a large leakage, the 

pressure gauge will drop quickly.
2.If there are no large leakages, charge the piping with 

nitrogen  at  1.5Mpa  and  leave  for  at  least  3  minutes. 

Observe the pressure gauge to check for small leakages. 

If there is a small leakage, the pressure gauge will drop 

distinctly.

3.If there are no small leakages, charge the piping with 

nitrogen at 4.2 MPa and leave for at least 24 hours to 

check  for  micro  leakages.  Micro  leakages  are  difficult 

to  detect.  To  check  for  micro  leakages,  allow  for  any 

change in ambient temperature over the test period by 

adjusting the reference pressure by 0.01Mpa per 1°C of 

temperature  difference.  Adjusted  reference  pressure  = 

Pressure at pressuri (temperature at observation 

–  temperature  at  pressurization)  x  0.01Mpa.  Compare 

the  observed  pressure  with  the  adjusted  reference 

pressure.  If  they  are  the  same,  the  piping  has  passed 

the gas tightness test. If the observed pressure is lower 

than the adjusted reference pressure, the piping has a 

micro leakage.

4.If the leakage is detected, refer to following part “Leak 

detection”. Once the leak has been found and fixed, the 

gas tightness test should be repeated.
5.If  not  continuing  straight  to  vacuum  drying  once 

the  gas  tightness  test  is  complete,  reduce  the 

system  pressure  to  0.5-0.8MPa  and  leave  the  system 

pressurized  until  ready  to  carry  out  the  vacuum  drying 

procedure.

 

Gas side of 

stop valve

Liquid side of 

stop valve

Gas pipe

Liquid pipe

Indoor unit

Outdoor unit

Figure 14-16

14.3.4 Leak Test

The general methods for identifying the source of a leak 

are as follows:
1. Audio detection: relatively large leaks are audible.
2. Touch detection: place your hand at joints to feel for 

escaping gas. 
3.  Soapy  water  detection:  small  leaks  can  be  detected 

by the formation of bubbles when soapy water is applied 

to a joint.
4.Electronic  leak  detector  detection:  electronic  leak 

detector shall be used to check whether air leaks at each 

joint.

14.3.5 Vacuum Drying

Vacuum drying should be performed in order to remove 

moisture  and  non-condensable  gases  from  the  system. 

Removing moisture prevents ice formation and oxidization 

of  copper  piping  or  other  internal  components.  The 

presence  of  ice  particles  in  the  system  would  cause 

abnormal  operation,  whilst  particles  of  oxidized  copper 

can  cause  compressor  damage.  The  presence  of  non-

condensable gases in the system would lead to pressure 

fluctuations and poor heat exchange performance.
Vacuum drying also provides additional leak detection (in 

addition to the gas tightness test).

●  Before performing vacuum drying, make sure 

that all the outdoor unit stop valves are firmly 

closed.

●  Once the vacuum drying is complete and the 

vacuum pump is stopped, the low pressure in 

the piping could suck vacuum pump lubricant 

into  the  air  conditioning  system.  The  same 

could  happen  if  the  vacuum  pump  stops 

unexpectedly  during  the  vacuum  drying 

procedure.  Mixing  of  pump  lubricant  with 

compressor oil could cause compressor 

malfunction. Therefore, a check valve should 

be  used  to  prevent  vacuum  pump  lubricant 

seeping into the piping system.

●  Vacuumize using a vacuum pump. Do not use 

refrigerant gas to discharge air.

●  To  prevent  the  entry  of  impurities,  the  R32 

special tool must be used to ensure compression 

strength  is  maintained.  Use  a  charging  hose 

with a top rod to connect to the access hole of 

the stop valve or the refrigerant charging port.

 NOTE

Содержание KMF-80 DVR5

Страница 1: ...lly and keep it for future reference All the pictures in this manual are for illustration purpose only OWNER S INSTALLATION MANUAL Mini Amazon VRF ODU KMF 80 DVR5 KMF 100 DVR5 KMF 120 DVR5 KMF 140 DVR...

Страница 2: ...ll prevail The units comply with IEC 61000 3 12 NOTE a b c 0 00 1 00 2 00 3 00 4 00 5 00 6 00 7 00 8 00 5 15 25 35 45 55 65 Minimum room area Amin m2 Maximum refrigerant charge Mmax kg Figure 1 Curve...

Страница 3: ...2 1 601 4 803 5 871 64 2 731 7 7 7 7 130 3 892 7 7 7 7 23 1 637 4 911 6 003 65 2 752 7 7 7 7 135 3 966 7 7 7 7 24 1 672 5 017 6 132 66 2 773 7 7 7 7 140 4 039 7 7 7 7 25 1 706 5 12 6 258 67 2 794 7 7...

Страница 4: ...edure 10 6 Maintenance and Repair 11 6 1 About Refrigerant 11 6 2 After sales Service and Warranty 11 7 Troubleshooting 12 7 1 Air Conditioner Problems and Causes 12 7 2 Remote Controller Problems and...

Страница 5: ...Cable Connection 36 17 Configuration 37 17 1 Overview 37 17 2 Functions of SW1 and SW2 Buttons 37 17 3 S2 DIP Switch Function 37 17 4 Display Function 37 18 Commissioning 38 18 1 Overview 38 18 2 Thi...

Страница 6: ...nguages are translations 2 Safety Signs 2 1 Explanation of Safety Signs The precautions and things to note in this document involve very important information Please read them carefully DANGER Indicat...

Страница 7: ...d in a well ventilated location other than the occupied space such as in the open air For installation of the indoor unit refer to the corresponding installation and operation manual If an indoor unit...

Страница 8: ...rrespondence of the maximum refrigerant charge with the minimum room area Amin is shown in Figure 1 and Table 1 And different values are used for different indoor installation heights The VRF IDU inst...

Страница 9: ...ety checks are necessary to minimize the risk of ignition When repairing the refrigerating system comply with the following precautions prior to conducting work on the system shall be undertaken accor...

Страница 10: ...turer Other parts may result in the ignition of refrigerant which has leaked into the surroundings Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or...

Страница 11: ...has been cleaned and checked Equipment shall be labeled stating that it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equi...

Страница 12: ...ctor or telephone earth wire CAUTION In order to avoid injury do not remove the fan guard of the outdoor unit Do not operate the air conditioner with wet hands An electric shock may happen Do not touc...

Страница 13: ...b a b b d c e d c e d c e Figure 4 1 Case 2 ODU is connected with VRF IDU and DHW kit DHW kit cannot be independently connected with the ODU a Heat pump outdoor unit b Refrigerant piping c VRF indoor...

Страница 14: ...t will automatically restart its operation when the power supply resumes 5 2 2 Cooling Heating DHW Fan Only and Auto The IDU of the air conditioning system can be controlled separately but the ODU can...

Страница 15: ...lic module will change and the electric heating of the DHW kit and the hydraulic module will also automatically start These measures are all aimed at preventing the outlet water temperature from falli...

Страница 16: ...s when it accidentally leaks and comes in contact with flammable substances generated by heaters and burning devices in the room Qualified maintenance personnel must verify that the point of leakage h...

Страница 17: ...ly Clean the air filter and external shell of the unit Please contact the installation or maintenance personnel to clean the air filter and external shell of the indoor unit The installation operation...

Страница 18: ...mpletely closed Leakage of refrigerant or lack of refrigerant Use heating devices Close doors and windows Check for leakage and correctly recharge refrigerant Table 7 2 Symptom Troubleshooting Solutio...

Страница 19: ...of refrigerant that occurs when it stops flowing or its flow changes Symptom 4 3 ODU When the tone of operating noise changes the noise is caused by the change of frequency Symptom 5 Dust comes out o...

Страница 20: ...installation work properly according to the Installation Manual Incorrect installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room take ap...

Страница 21: ...that is sufficient to support the weight of the unit and with a width of at least 20 mm Images are for reference purpose only Please refer to the actual product The belt must have enough strength to...

Страница 22: ...of ODU HP Number of IDUs Combination ratio of VRF IDU Number of hydraulic modules 8 3 0 2 4 50 100 1 10 3 6 2 6 50 100 1 12 4 5 2 7 50 100 1 14 5 0 2 8 50 100 1 16 6 0 2 9 50 100 1 Case 4 ODU is indi...

Страница 23: ...e interferes your neighbour s everyday life A place that is too weak to bear the weight of the unit An uneven place Insufficient ventilation place A place near a private power station or high frequenc...

Страница 24: ...e wall of the building 2000 Caution 13 1 3 Requirements for ODU Installation in Cold Regions Protect the ODU from direct snowfall and be careful not to let the ODU become covered in snow Snow may accu...

Страница 25: ...ts using nuts with resin washers If the coating in the fastening area is peeled off the metal is prone to rusting Resin washer Caution Build a concrete base according to the specifications of the ODU...

Страница 26: ...al R32 does not contain fluorine does not destroy the ozone layer and does not deplete the ozone layer that protects the earth from harmful ultraviolet radiation However if it is released R32 can also...

Страница 27: ...rence for Refrigerant Piping Table 14 2 Permitted value Piping Piping Length Length of refrigerant pipe actual 60 m 8 kW 80 m 10 12 kW 100 m 14 16 kW L1 L2 L3 L4 L5 a b c d e f Piping length between t...

Страница 28: ...d gas side is 90 m as listed in Table 14 5 Caution Pipe diameter and branch joints between ODU and IDU according to downstream IDU DHW kit and hydraulic module need not to be included Table 14 6 Total...

Страница 29: ...as and liquid pipe size of a to f are 12 7 and 6 35 respectively Example 2 of refrigerant piping selection ODU N1 28 N3 28 N5 28 N6 60 N2 28 N4 28 A B D E C a b c d L1 L2 L5 L3 L4 e f Figure 14 3 The...

Страница 30: ...ze from a to c is respectively 12 7 and 6 35 According to Table 14 7 the pipe size d is respectively 15 9 and 9 52 14 2 Connecting Refrigerant Piping 14 2 1 Things to Note When Connecting the Refriger...

Страница 31: ...Gas pipe Provided on site Liquid pipe Provided on site Side out pipe please remove the L shaped metal plate otherwise wiring cannot be completed Back out pipe please wipe off the bracket rubber beside...

Страница 32: ...t be used for flushing Use of such gases may result in fire or explosion CAUTION The liquid and gas sides must be flushed simultaneously The flushing procedure is as follows 1 Cover the inlets and out...

Страница 33: ...vacuum drying once the gas tightness test is complete reduce the system pressure to 0 5 0 8MPa and leave the system pressurized until ready to carry out the vacuum drying procedure Gas side of stop va...

Страница 34: ...on the installation environment 14 3 6 1 Selection of insulation material thickness Condensed water may form on the surface of the insulation layer Table 14 10 Piping size Humidity 80 RH Thickness Hu...

Страница 35: ...No 0 14 No Yes 0 333 16 No Yes 0 380 Table 15 4 Total additional charge R is equal to the sum of R1 R2 and R3 Calculate the refrigerant charge according to the following formula R R1 R2 R3 Determine t...

Страница 36: ...ker 3 The wire carrying capacity is for reference purposes only The modification factor of the actual carrying ca pacity depends on cable type and length lead through method and the environment for ca...

Страница 37: ...main circuit breaker or safety device that can disconnect all polarities must be installed and it can be completely disconnected when the voltage gets too high Wiring must be carried out in strict ac...

Страница 38: ...ompleted by professionals Communication wires between IDUs including multiple IDUs DHW kits and hydraulic modules and ODUs shall only be led out from ODUs When a single communication wire is not long...

Страница 39: ...14 1 and EN 55014 2 Caution Communication Wiring Diagram when ODU is connected with VRF IDU and DHW kit Figure 16 5 Communication wire Power cable ODU L2 Power distribution cabinet Power distribution...

Страница 40: ...be used Connect the shielding nets at both ends of the shielded cable to the sheet metal of the electrical control box Applicable standards EN 55014 1 and EN 55014 2 Caution Communication Wiring Diagr...

Страница 41: ...he ground and you must turn off the power supply when you are connecting the ground line before you connect the power cable Before installing the screws you must first comb through the path along the...

Страница 42: ...nabled priority default 1 2 21 3 Heating mode priority 1 2 21 3 In response to heating mode only 17 4 Display Function There are buttons 8 16 kW for SW2 on the ODU check board main control board The d...

Страница 43: ...wing items first After all following checks have been completed you must shut down the unit This is the only way to start the unit again Table 18 1 Installation Check if the unit is installed correctl...

Страница 44: ...ect to automatic diagnosis during the test run If the ODU cannot start or stops abnormally during the test run conduct troubleshooting according to the table of error codes and perform the test run ag...

Страница 45: ...12 Cooling ambient temperature lower than 16 C No EP 13 DC bus voltage protection No F1 14 L L0 L1 fault occurring 3 times in 1 hour Yes H4 15 Online IDU quantity decrease increase No H7 16 Radiator...

Страница 46: ...arm where refrigerant is usually stored IDU IDU Refrigerant has leaked throughout the room Refrigerant is used out A Ventilation opening Figure 19 1 Table 19 2 Model Factory charge Refrigerant kg tons...

Страница 47: ...onent name 1 Compressor 2 Muffler 3 High pressure switch 4 4 way valve ST1 5 Fan 6 Heat exchanger 7 Electronic expansion valve EXVA 8 Stop valve liquid side 9 Stop valve gas side 10 Gas liquid separat...

Страница 48: ...or 2 Muffler 3 High pressure switch 4 4 way valve ST1 5 Fan 6 Heat exchanger 7 Electronic expansion valve EXVA 8 Stop valve liquid side 9 Stop valve gas side 10 Gas liquid separator 11 Low pressure sw...

Страница 49: ...e 1 Compressor 2 Muffler 3 High pressure switch 4 4 way valve ST1 5 Fan 6 Heat exchanger 7 Electronic expansion valve EXVA 8 Stop valve liquid side 9 Stop valve gas side 10 Gas liquid separator 11 Low...

Страница 50: ...me 1 Compressor 2 Oil separator 3 High pressure switch 4 4 way valve ST1 5 Fan 6 Heat exchanger 7 Electronic expansion valve EXVA 8 Stop valve liquid side 9 Stop valve gas side 10 Gas liquid separator...

Страница 51: ...rage season A Annual electricity consumption in heating QHE average season kWh a 1821 Design load in heating mode Pdesignh kW 5 20 Declared capacity at reference design condition heating average seaso...

Страница 52: ...nual electricity consumption in heating QHE average season kWh a 1984 Design load in heating mode Pdesignh kW 5 60 Declared capacity at reference design condition heating average season kW 9 00 Back u...

Страница 53: ...Pdc 7 20 kW Tj 35 C EERd 3 23 Tj 30 C Pdc 5 31 kW Tj 30 C EERd 5 30 Tj 25 C Pdc 3 41 kW Tj 25 C EERd 8 50 Tj 20 C Pdc 3 10 kW Tj 20 C EERd 9 90 Degradation co efficient for air conditioners Cdc 0 25...

Страница 54: ...W Tj 2 C COPd 3 85 Tj 7 C Pdh 1 80 kW Tj 7 C COPd 5 10 Tj 12 C Pdh 0 80 kW Tj 12 C COPd 6 90 Tbiv bivalent temperature Pdh 5 20 kW Tbiv bivalent temperature COPd 2 10 TOL operation temperature Pdh 5 2...

Страница 55: ...00 kW Tj 35 C EERd 3 06 Tj 30 C Pdc 6 70 kW Tj 30 C EERd 5 10 Tj 25 C Pdc 4 30 kW Tj 25 C EERd 7 70 Tj 20 C Pdc 3 37 kW Tj 20 C EERd 10 50 Degradation co efficient for air conditioners Cdc 0 25 Power...

Страница 56: ...C COPd 3 80 Tj 7 C Pdh 1 94 kW Tj 7 C COPd 5 10 Tj 12 C Pdh 0 87 kW Tj 12 C COPd 6 30 Tbiv bivalent temperature Pdh 5 60 kW Tbiv bivalent temperature COPd 2 20 TOL operation temperature Pdh 5 60 kW T...

Страница 57: ...Pdc 12 30 kW Tj 35 C EERd 3 20 Tj 30 C Pdc 9 00 kW Tj 30 C EERd 5 20 Tj 25 C Pdc 5 80 kW Tj 25 C EERd 10 00 Tj 20 C Pdc 4 10 kW Tj 20 C EERd 15 00 Degradation co efficient for air conditioners Cdc 0...

Страница 58: ...kW Tj 2 C COPd 4 13 Tj 7 C Pdh 2 70 kW Tj 7 C COPd 6 20 Tj 12 C Pdh 1 20 kW Tj 12 C COPd 8 70 Tbiv bivalent temperature Pdh 7 80 kW Tbiv bivalent temperature COPd 2 10 TOL operation temperature Pdh 7...

Страница 59: ...Pdc 14 00 kW Tj 35 C EERd 3 23 Tj 30 C Pdc 10 30 kW Tj 30 C EERd 5 30 Tj 25 C Pdc 6 60 kW Tj 25 C EERd 9 10 Tj 20 C Pdc 6 00 kW Tj 20 C EERd 11 10 Degradation co efficient for air conditioners Cdc 0...

Страница 60: ...kW Tj 2 C COPd 4 45 Tj 7 C Pdh 3 46 kW Tj 7 C COPd 6 00 Tj 12 C Pdh 1 54 kW Tj 12 C COPd 7 50 Tbiv bivalent temperature Pdh 10 00 kW Tbiv bivalent temperature COPd 2 30 TOL operation temperature Pdh 1...

Страница 61: ...Pdc 15 50 kW Tj 35 C EERd 3 02 Tj 30 C Pdc 11 40 kW Tj 30 C EERd 4 60 Tj 25 C Pdc 7 30 kW Tj 25 C EERd 8 60 Tj 20 C Pdc 5 20 kW Tj 20 C EERd 12 00 Degradation co efficient for air conditioners Cdc 0...

Страница 62: ...kW Tj 2 C COPd 3 85 Tj 7 C Pdh 3 81 kW Tj 7 C COPd 6 65 Tj 12 C Pdh 1 69 kW Tj 12 C COPd 8 50 Tbiv bivalent temperature Pdh 11 00 kW Tbiv bivalent temperature COPd 2 20 TOL operation temperature Pdh 1...

Страница 63: ...iciency 0 211 10 2 Flow rate s at optimum energy efficiency m3 h 4891 10 3 Pressure s at optimum energy efficiency Pa 50 11 Rotations per minute R P M at the optimum energy efficiency point 800r min 1...

Страница 64: ...rgy efficiency 0 198 10 2 Flow rate s at optimum energy efficiency m3 h 4886 10 3 Pressure s at optimum energy efficiency Pa 50 11 Rotations per minute R P M at the optimum energy efficiency point 800...

Страница 65: ...ciency 0 288 10 2 Flow rate s at optimum energy efficiency m3 h 5615 10 3 Pressure s at optimum energy efficiency Pa 60 11 Rotations per minute R P M at the optimum energy efficiency point 900r min 12...

Страница 66: ...rgy efficiency 0 294 10 2 Flow rate s at optimum energy efficiency m3 h 5448 10 3 Pressure s at optimum energy efficiency Pa 65 11 Rotations per minute R P M at the optimum energy efficiency point 900...

Страница 67: ...16127000005207...

Страница 68: ......

Отзывы: