80
Figure 4-4.6: Inverter module terminals
4.13.7 xL1/xL4 troubleshooting
Step 1: Check inverter module
▪ Check the DC voltage between terminals P and N. The normal value is 537-586V (power supply voltage specification:
380~415V 3N~). If the voltage is lower than 300V, go to Step 2.
Figure 4-4.7: Inverter module terminals
P
L1
L2
U
L3
V
W
N
N
P