3 Error Code Table
Table 4-3.1: Error Code Table (30kW and 60kW units)
Error code
Serial number
1
Content
Remarks
E0
1
Main control parameter memory EEPROM failure
Displayed on main PCB and user
interface
E1
2
Phase sequence failure of main control board check
Displayed on main PCB and user
interface
E2
3
Communication failure between master and the HMI
Displayed on main PCB and user
interface
3
Communication failure between master and the slave
Displayed on main PCB and user
interface
E3
4
Total water outlet temperature sensor (Tw) failure (displayed on master
unit only)
Displayed on main PCB and user
interface
E4
5
Unit water outlet temperature sensor (Two) failure
Displayed on main PCB and user
interface
E5
6
1E5 condenser tube temperature sensor T3A failure
Displayed on main PCB and user
interface
6
2E5 condenser tube temperature sensor T3B failure
Displayed on main PCB and user
interface
E7
8
Ambient temperature sensor (T4) failure
Displayed on main PCB and user
interface
E8
9
Power supply phase sequence protector output error
Displayed on main PCB and user
interface
E9
10
Water flow detection failure
Displayed on main PCB and user
interface
Eb
12
1Eb --> Taf1 cooling evaporator low-temperature anti-freeze protection
sensor failure
Displayed on main PCB and user
interface
12
2Eb --> Taf2 cooling evaporator low-temperature anti-freeze protection
sensor failure
Displayed on main PCB and user
interface
EC
13
Slave unit module reduction
Displayed on user interface
1Ed --> A system discharge temperature sensor failure
Displayed on main PCB and user
interface
2Ed --> B system discharge temperature sensor failure
Displayed on main PCB and user
interface
EF
16
Unit water return temperature sensor (Twi) failure
Displayed on main PCB and user
interface
EH
17
System self-check failure alarm
Displayed on main PCB and user
interface
EP
19
Discharge temperature sensor failure alarm
Displayed on main PCB and user
interface
EU
20
Tz/7 Coil final outlet temperature sensor error
Displayed on main PCB and user
interface
P0
21
System high-pressure protection or discharge temperature protection
Displayed on main PCB and user
interface
Table continued on next page …