5.2 Normal Operating Parameters of Refrigerant System
Under the following conditions, the operating parameters given in Tables 5-5.4 and 5-5.5 should be observed:
▪ If the outdoor ambient temperature is high, the system is being run in normal cooling mode with the following
settings: temperature 5°C.
▪ If the outdoor ambient temperature is low, the system is being run in heating mode with the following settings:
temperature 55°C.
▪ The system has been running normally for more than 30 minutes.
Table 5-5.4: Outdoor unit in normal cooling mode operating parameters
Outdoor ambient temperature
°C
< 10
10 to 25
25 to 35
35 to 43
Average discharge temperature
°C
60-90
65-95
70-99
75-108
Average discharge superheat
°C
28-38
28-40
29-42
30-46
Discharge pressure
Mpa
1.8-2.9
1.9-3.2
2.0-3.8
2.6-3.9
Average suction superheat
°C
3-7
4-9
5-11
6-12
Suction pressure
Mpa
0.6-0.9
0.7-1.0
0.8-1.5
1.0-1.3
Average suction temperature
°C
7-18
7-20
8-22
20-25
T3
°C
0-15
15-35
30-48
48-54
Tz/7
°C
20-25
12-30
28-46
44-52
Taf
°C
5-25
5-25
5-25
5-25
T6A/B
°C
-2-17
1-20
3-35
5-40
Twi
°C
10-25
10-25
10-25
10-25
Two
°C
5-20
5-20
5-20
5-20
Tw
°C
5-20
5-20
5-20
5-20
DC fan motor current
A
0.2-6
2-6
3-6
4-6
DC inverter compressor current
A
6-12
2-16
3-17
4-18
Table 5-5.5: Outdoor unit in heating mode operating parameters
Outdoor ambient temperature
°C
< -10
-10 to 0
0 to 7
7 to 20
> 20
Average discharge temperature
°C
50-104
55-103
60-103
65-102
70-100
Average discharge superheat
°C
35-55
35-55
32-50
34-50
35-50
Discharge pressure
Mpa
1.8-2.9
1.9-2.9
1.9-3.4
2.2-3.6
Average suction superheat
°C
-2-0
-2-2
-1-4
0-6
1-8
Suction pressure
Mpa
0.2-0.5
0.3-0.7
0.4-0.9
0.6-1.2
0.8-1.4
Average suction temperature
°C
-22 to -11
-16 to 2
-10 to 5
0 to 15
5 to 18
T3
°C
-20 to -11
-16 to 0
-10 to 2
1 to 12
5 to 15
Tz/7
°C
-19 to -4
-14 to 1
-5 to -2
1 to 6
2 to 10
Taf
°C
20-45
20-50
20-54
20-54
20-54
T6A/B
°C
-2-20
0-25
3-35
8-40
13-43
Twi
°C
20-40
20-45
20-50
20-50
20-50
Two
°C
24-45
25-50
25-54
25-54
25-54
Tw
°C
25-45
25-50
25-54
25-54
25-54
DC fan motor current
A
5-6
4-6
2-6
0.5-6
0.3-6
DC inverter compressor current
A
1-15
1-16
1-17
2-18
2-18
Ver. 2019-10