34
6.8 Air Side Heat Exchanger High Temperature Protection Control
This control protects the air side heat exchanger from high temperature.
Figure 3-6.9: Air side heat exchanger high temperature protection control
1
Figure 3-6.10: Air side heat exchanger temperature protection control
2
Normal operation
T3 > 60°C
T3 < 50°C
High temperature protection, error code P7 is displayed
Note:
1. T3: Air side heat exchanger refrigerant outlet temperature
When the air side heat exchanger refrigerant outlet temperature (T3) rises above 60°C, the system displays P7 protection
and all the units stop running. When the air side heat exchanger refrigerant outlet temperature (T3) drops below 50°C, the
compressor enters re-start control.
Normal operation
Tz/7 ≥ 61°C
Tz/7 < 58°C
High temperature protection, error code P7 is displayed
Note:
1. Tz/7: Air side heat exchanger refrigerant total outlet temperature
When the air side heat exchanger refrigerant total outlet temperature (Tz/7) temperature rises at or above 61°C, the
system displays P7 protection and the unit stops running. When the air side heat exchanger refrigerant total outlet
temperature (Tz/7) temperature drops below 58°C, the compressor enters re-start control.
6.9 Water Side Heat Exchanger Temperature Difference Protection Control
This control protects the water side heat exchanger from ice formation.
Figure 3-6.11: Water side heat exchanger temperature difference protection control
Normal operation
│ Twi-Two │ ≥ 12°C
│ Twi-Two │ < 6°C
Temperature difference protection, error code P9 is displayed
When P9 protection occurs 3 times
in 60 minutes, a manual system
restart is required before the system
can resume operation.
Notes:
1. Twi: Water side heat exchanger inlet temperature
2. Two: Water side heat exchanger outlet temperature
When the temperature difference rises at or above 12°C, the system displays P9 protection and all the units stop running.
When the Temperature difference drops below 6°C, the compressor enters re-start control.