![Kaysun KEM-30 DRS4 Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/kaysun/kem-30-drs4/kem-30-drs4_service-manual_659094103.webp)
102
4.23 H5 Troubleshooting
4.23.1 Digital display output
4.23.2 Description
▪ Abnormal power supply voltage.
▪ All units stop running.
▪ Error code is only displayed on main PCB and user interface.
4.23.3 Possible causes
▪ Outdoor unit power supply voltage at or above260V or drops below 165V or a phase is missing.
▪ Loosened wiring within electric control box.
▪ High voltage circuit error.
▪ Main PCB damaged.