DN1611-1809
3
KT-NCC Installation Manual
Pre-Installation Information
Copyright Info
© 2018 Tyco Security Products. All Rights Reserved. All specifications were current as of publication
date and are subject to change without notice. EntraPass, Kantech and the Kantech logo are trademarks
of Tyco International Ltd. and its Respective Companies.
Safety
Instructions
Important:
NEVER INSTALL THE EQUIPMENT DURING A LIGHTNING STORM!
This equipment, KT-NCC NETWORK COMMUNICATIONS CONTROLLER Model KT-NCC-EU shall be
used installed and used within an environment that provides the pollution degree max 2 and over
voltages category II NON HAZARDOUS LOCATIONS, INDOOR only. The equipment is FIXED and
PERMANENTLY CONNECTED and is designed to be installed by Service Persons only; [service person
is defined as a person having the appropriate technical training and experience necessary to be aware of
hazards to which that person may be exposed in performing a task and of measures to minimize the risks
to that person or other persons.] The equipment is installed in a metallic cabinet that meets the applicable
requirements for a FIRE ENCLOSURE.
1. The
connection to the mains supply
must be made as per the local authorities rules and regulations:
In the UK as per BS6701. An appropriate disconnect device must be provided as part of the building
installation. Where it is not possible to rely on the identification of the NEUTRAL in the AC MAINS
SUPPLY, the disconnecting device must disconnect both poles simultaneously (LINE and NEUTRAL).
2. AVOID
setting up
the equipment near heaters, air conditioners, ventilators, and/or refrigerators;
DO NOT select a place that exposes your KT-NCC to direct sunlight, excessive heat, moisture, vapors,
chemicals or dust.
3. If
during the installation
a knockout on the cabinet is removed, it is the installer's responsibility to
ensure that the same degree of protection for the cabinet is provided by the use of bushings, fittings,
adequate sealant, etc.
4. The metallic
cabinet must be secured to the building structure before
operation. Use four (4)
stainless steel tapping screws #8, 32 mm (1.25 in) to mount the cabinet.
5. Regarding the
power supply, it is permanently connected
, fail safe, with double or reinforced
insulation between primary and secondary circuits. In EU countries it must meet the applicable
requirements of the Low Voltage Directive and is protected as per the EN60950-1: 2001 Standard
Requirements. In all other countries, it must be of an approved type acceptable to the local authorities.
6. The
ground connection
must be as shown within the included diagram, or equivalent.
7.
Internal wiring
must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections;
- Loosening of terminal; connections;
- Damage of conductor insulation.
8. It is the end-user and/or installer's responsibility to ensure that the disposal of the used batteries is
made according to the waste recovery and recycling regulations applicable to the intended market.
9. There are
no serviceable parts within the equipment
; For any issues regarding the equipment
please contact your installer.
10.
DISCONNECT POWER BEFORE SERVICING
.