DN1611-1809
17
KT-NCC Installation Manual
Connecting the
Relays (cont’d)
Note:
Relay #2 is located at the bottom left of the KT-NCC PCB.
For more information on configuring relays, please refer to the
EntraPass Global Edition Reference
Manual,
DN1316.
Installing the KT-
3LED-PLATE
For the arm/disarm operation, install the 3-LED plate (Kantech part number KT-3LED-PLATE) according
to UL 1076 standards by following this procedure:
For the KT-400 Section:
1. Connect the LED black wire to GND AUX (which is associated with the green and red LEDs).
2. Connect the LED red wire to NO Relays (which is associated with the red LED).
3. Connect the LED red wire to NC Relays (which is associated with the green LED).
4. From AUX, use the 12-V cable and connect it to C Relays (which are associated with the red and
green LEDs).
For the KT-300 Section:
1. Connect the LED black wire to GND AUX (which is associated with the red and green LEDs).
2. Connect the LED red wire to RL2 (which is associated with the red LED).
3. Connect the LED red wire to RL1 (which is associated with the green LED). To do this, you need to
click the
Devices
tab and, from the menu
Relay,
select
Reverse
from the
General tab.
Note:
The green LED corresponds to
Ready to arm
or
Prevent arming
.
Note:
When the red LED is ON, it corresponds to the
arm
function, and when the red LED is OFF, it
corresponds to the
disarm
function. The system cannot be armed or disarmed when the
Ready to arm
green LED is OFF.
The electrical plate, with 22 AWG wires, made of stainless steel is considered as a standard.
Note:
The 3-LED plate must be located near the reader(s) that is(are) designed to arm or disarm the
alarm system. It must be within the secured side of the customer’s premises.
EntraPass
Configuration
1. From
Devices,
in the
Gateway
dialog box, select the
Onboard Relays
tab, and then select
Server
Communication failed
from the
Onboard relay
drop-down menu. Click
Save
, then
Close
.
2. From
Definition,
in the
Alarm System
dialog box,
select the
Input
tab, and assign the appropriate
inputs in both the
Alarm level #1
and
Prevent arming
fields. To confirm, click
OK, Save
then
Close.
3. From
Definition
, in the
Alarm System
dialog box, in the
Control relay
tab, in the
System status -
relay,
choose the wanted replay to use in order to enable
Ready to Arm
. To confirm, click
OK
.
Close.
Note:
For additional software configuration, please refer to
EntraPass Global Edition Reference
Manual
, DN1316.
Hardware Configuration:
•
From the KT-NCC selected relays (C and NO) as defined previously in the EntraPass
configuration, connect a 2-wire cable to the selected input door.
•
For the KT-400, use C and Z inputs.
•
For the KT-300, use C and the selected input.
Note:
The polarity has no importance.
Содержание KT-NCC
Страница 1: ...DN1611 1809 KT NCC Network Communications Controller Installation Manual ...
Страница 41: ...DN1611 1809 41 Figure 24 KT NCC Wiring Diagram for Europe and Asia ...
Страница 45: ...DN1611 1809 45 ...
Страница 46: ... 2018 Tyco Security Products All Rights Reserved www kantech com DN1611 1809 ...