
MULTICAL® 402
Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016
35
6.5
Operating pressure of MULTICAL
®
In connection with installations it has proved practical to work with minimum the pressures mentioned below:
402
Nominal flow q
p
Recommended back
pressure
Max. flow qs
Recommended back
pressure
[m³/h]
[bar]
[m³/h]
[bar]
0.6
1
1.2
2
1.5
1.5
3
2.5
2.5
1
5
2
3.5
1
7
2
6
1.5
12
2.5
10
1
20
2
15
1.5
30
2.5
Table 6
The purpose of recommended back pressure is to avoid measuring errors as a result of cavitation or air in the
water.
It is not necessarily cavitation in the sensor itself, but also bubbles from cavitating pumps and regulating valves
mounted before the sensor. It can take some time before such bubbles have been absorbed by the water.
Furthermore, water can include dissolved air. The amount of air which can be dissolved in water depends on
pressure and temperature. This means that air bubbles can be formed due to pressure drop, e.g. caused by a
velocity rise in a contraction or above the meter.
The risk of these factors affecting accuracy is reduced by maintaining a fair pressure in the installation.
In relation to above table, the steam pressure at current temperature must also be considered. Table 6 applies to
temperatures up to approx. 80°C. Furthermore, it must be considered that the above-mentioned pressure is the
back pressure at the sensor and that the pressure is lower under a contraction than before
This can be explained by combining the continuity equation and Bernoulli’s equation. The total energy from the
flow will be the same at any cross section. It can be reduced to: P + ½
ρ
v
one (e.g. cones). This
means that the pressure – when measured elsewhere - might be different from the pressure at the sensor.
2
When dimensioning the flow sensor you must take this into consideration, especially if the sensor is used within
the scope of EN 1434 between q
= constant.
p
and q
s
, and in case of heavy contractions of the pipe.
Diagram 3
0
0,5
1
1,5
2
2,5
3
80
85
90
95
100
105
110
115
120
125
130
[b
ar
]
[°C]
Steam pressure
Содержание MULTICAL 402
Страница 1: ...MULTICAL 402 Technical Description...
Страница 2: ...MULTICAL 402 2 Kamstrup A S Technical Description 5512 742_M1_GB_01 2016...
Страница 109: ...MULTICAL 402 Kamstrup A S Technical Description 5512 742_M1_GB_01 2016 109...
Страница 113: ...MULTICAL 402 Kamstrup A S Technical Description 5512 742_M1_GB_01 2016 113...