35
(2) After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2
protection cumulates up to 90 minutes.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to
normal heating mode.
(1) The defrosting time is reached to the setting value.
(2) The compressor current reaches or overs I
DEFROST
for 7 seconds.
I
DEFROST
=3.5A for 7k,9k models, I
DEFROST
=7.5A for 18k models.
Defrosting action
:
About the setting defrosting time:
(1) Condition 1 of defrosting;
If case B happens before case A and lasts till case A happens, the setting defrosting time is 10
minutes.Otherwise the defrosting time is 7.5 minutes.
(2) Condition 2 of defrosting.
The defrosting time is 10 minutes.
(3)
No matter what condition of defrosting is, if the defrosting time keeps 7.5 minutes for 3 times, it will
Содержание R ON-OFF series
Страница 1: ...SPLIT WALL MOUNTED TYPE R ON OFF SERIES...
Страница 8: ...6 2 Function...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 14: ...12 4 Refrigerant Cycle Diagram For heat pump models...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units KSR1 07HRN1 QC2 A KSR1 09HRN1 QC2 A KSR1 18HRN1 QB8...
Страница 16: ...14 KSR1 21HRN1 QB8W KSR1 21CR QB6W KSR1 21HR QB6W KSR1 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units KOK1 07HN1 QC2 KOA1 09HN1 QC2...
Страница 18: ...16 KOE 18HN1 QB8...
Страница 19: ...17 KOF 21HN1 QB8W K0F2 21C QB6W KOP 21H QB6W...
Страница 20: ...18 KOF2 24HN1 QB8W...