When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes(4 minutes for 21k,24k models),
the compressor and outdoor fan will shut off.
When T2 is higher than TE6, the compressor and outdoor fan will restart up.
While TE5=4
℃
, TE6=
10
℃
for KSR1-07HRN1-QC2(A),
KSR1-09HRN1-QC2(A) models; TE5=3
℃
,
TE6=14
℃
for KSR1-18HRN1-QB8 model.
TE5=2
℃
, TE6=
12
℃
for KSR1-21HRN1-QB8W , KSR1-21CR-QB6W , KSR1-21HR-QB6W
KSR1-24HRN1-QB8W models.
8.4.2.5 Condenser high temperature T3 protection.(only for 21k,24k heat pump models)
T3
TE10
Off
On
TE11
When T3≥TE10, the compressor will shut off. When T3
<
TE11,the compressor will restart.
TE10=65
℃
, TE11=55
℃
.
8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
For 21k,24k models, everytime the compressors start up, they will keep running for
△
t
minutes(protections are active) and then follow the below rules. (While
△
t=4.)
For other models, they will follow the below rules once the compressors start up:
When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is
lower than Tk, the compressor and outdoor fan will start up.
Tj=Ts+Tc
Tk=Ts+Tc-1. Tc=1
℃
for 7k,9k,18k models; Tc=4
℃
for 21k,24k models.
Содержание R ON-OFF series
Страница 1: ...SPLIT WALL MOUNTED TYPE R ON OFF SERIES...
Страница 8: ...6 2 Function...
Страница 11: ...9 3 Dimension 3 1 Indoor Units Figure 1 Figure 2...
Страница 14: ...12 4 Refrigerant Cycle Diagram For heat pump models...
Страница 15: ...13 5 Wiring Diagram 5 1 Indoor Units KSR1 07HRN1 QC2 A KSR1 09HRN1 QC2 A KSR1 18HRN1 QB8...
Страница 16: ...14 KSR1 21HRN1 QB8W KSR1 21CR QB6W KSR1 21HR QB6W KSR1 24HRN1 QB8W...
Страница 17: ...15 5 2 Outdoor Units KOK1 07HN1 QC2 KOA1 09HN1 QC2...
Страница 18: ...16 KOE 18HN1 QB8...
Страница 19: ...17 KOF 21HN1 QB8W K0F2 21C QB6W KOP 21H QB6W...
Страница 20: ...18 KOF2 24HN1 QB8W...