20
6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Connective pipe length
Air purging
Additional amount of
refrigerant
All
Less than 5m
Use vacuum pump
------------------
7k,9k,18k
More than 5m
Use vacuum pump
(Pipe length – 5) × 30g/m
21k,24k
More than 5m
Use vacuum pump
(Pipe length – 5) × 60g/m
Model
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
7k,9k
5
5
10
18k
5
8
15
21k,24k
5
10
20
Caution:
Capacity test is based on standard length and maximum allowance length is based on system
reliability.
Oil trap should be installed per 5-7 meters.