9.2.4 EEPROM parameter error diagnosis and solution
9.2.5 Zero crossing detection error
When such failure occurs, the main control board must have fault.
Replace indoor PCB
S
hut off the power supply and turn on it 5s later
The problem comes out again
Is the EEPROM chip plugged in indoor PCB well?
No
Correct the connection
Replace the main PCB of indoor unit