M thermal Split
82
202004
Midea
M t
her
ma
l S
pli
t Ser
vice M
anual
Procedure
4.19.4
P5
Water side heat exchanger water inlet /
outlet temperature sensor is loose
1
Yes
Ensure the temperature sensor is
connected properly
No
Water side heat exchanger water inlet /
outlet temperature sensor has
short-circuited or failed
2
Yes
Replace the temperature sensor
No
Water piping contains air
Yes
Purge air from the water system
3
No
The water flow rate is not sufficient,
caused by crushed or bent water piping,
incorrect pump speed setting, high
resistance in water piping or broken
expansion vessel
4
Yes
Inspect the system and fix the error
No
Replace hydronic box main PCB
Notes:
1. Water side heat exchanger water inlet temperature sensor and water side heat exchanger water outlet temperature sensor connections are port CN6
on the hydronic box main PCB (labeled10 in Figure 4-2.1 in Part4, 2.2 "Main PCB for Hydronic System").
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s
resistance characteristics table, the sensor has failed. Refer to Part 2, 1.2 “Hydronic Box Layout” and to Table 5-5.3 in Part 5, 5.1 “Temperature
Sensor Resistance Characteristics”.
3. Refer to the Split Engineering Data Book, Part 5, 15 “SPECIAL FUNCTIONS”.
4. Check water pressure on the manometer. If the water pressure is not > 1 bar, water flow is insufficient. Refer to Figures 2-1.7 and 2-1.8 in Part 2,
1.2 “Hydronic Box Layout”.
Midea CAC Confidential
M thermal Split
202004
83
4.20 Inverter module Troubleshooting for single-phase models
Digital display output
4.20.1
Description
4.20.2
Inverter module protection.
Split stops running.
Specific error code L0, L1, L2, L4, L5, L8, L9 is displayed on the user interface and the main control board of
refrigerant system.
Possible causes
4.20.3
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
PED board self checking fail.
Specific error codes for inverter module protection
4.20.4
Table 4-4.1: Specific error codes
Specific error code
Content
L0
Inverter module protection
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L4
MCE error(DC bus low or high voltage protection or software over current protection)
L5
Zero speed protection
L8
Compressor frequency variation greater than 15Hz within 1 second protection
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
Midea CAC Confidential
Split
Содержание KMK-60RY1
Страница 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Страница 2: ...Split...
Страница 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Страница 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Страница 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 113: ...Split...
Страница 114: ...kaisai com...