4.6 E5, E6, E9, EA Troubleshooting
Digital display output
4.6.1
Description
4.6.2
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor
error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
4.6.3
Temperature sensor not connected properly or has malfunctioned.
Damaged outdoor unit main PCB.