4.6 E5, E6, E9, EA Troubleshooting
Digital display output
4.6.1
Description
4.6.2
E5 indicates an air side heat exchanger refrigerant outlet temperature sensor
error.
E6 indicates an outdoor ambient temperature sensor error.
E9 indicates a suction pipe temperature sensor error.
EA indicates a discharge temperature sensor error.
Split stops running.
Error code is displayed on outdoor unit main PCB and user interface.
Possible causes
4.6.3
Temperature sensor not connected properly or has malfunctioned.
Damaged outdoor unit main PCB.
Midea CAC Confidential
M thermal Split
202004
61
Procedure
4.6.4
E5 / E6 / E9 / EA
Temperature sensor connection on
outdoor unit main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
2
Yes
Replace the sensor
No
Replace outdoor unit main PCB
Notes:
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connections are port CN9 on
the
KHA-06(08,10)RY1
outdoor unit refrigerant system main PCB (labeled 12 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN9 on the
KHA-12(14,16)RY3
outdoor unit refrigerant system main PCB (labeled 17 in Figure 4-2.4 in Part 4, 2.1 “Main PCBs for
Refrigerant System, Inverter Module”). Discharge pipe temperature sensor connection are port CN8 on the
KHA-06(08,10)RY1
outdoor unit
refrigerant system main PCB (labeled 15 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN4 on the
KHA-12(14,16)RY3
outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.4 in Part 4, 2.1 “Main PCBs for Refrigerant System,
Inverter Module”). Suction pipe temperature sensor connection are port CN1 on the
KHA-06(08,10)RY1
outdoor unit refrigerant system main
PCB (labeled 14 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN8 on the
KHA-12(14,16)RY3
outdoor unit
refrigerant system main PCB (labeled 16 in Figure 4-2.4 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter Module”).
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s
resistance
characteristics table, the sensor has failed. Refer to Table 4-5.1, and Table 4-5.2 in Part 4, 5.1 “Temperature Sensor Resistance Characteristics”.
Midea CAC Confidential
Split
Содержание KMK-60RY1
Страница 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Страница 2: ...Split...
Страница 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Страница 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Страница 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 113: ...Split...
Страница 114: ...kaisai com...