M thermal Split
20
202004
Midea
M t
her
ma
l S
pli
t Ser
vice M
anual
42rps
Target rotation speed
Time (s)
0
36rps
56rps 66rps
70rps
82rps
90s
60s
40s
40s
40s
120s
42rps
40s
Notes:
1
.
Once the first, 90-second stage of the program is complete, the program proceeds to the subsequent stages in a step-by-step fashion and exits when the
target rotation speed has been reached.
Figure 3-3.4: KHA-08(10)RY1 compressor startup program
1
when ambient temperature is at or below 11°C
38rps
Target rotation speed
Compressor rotation speed (rps)
Time (s)
0
32rps
42rps 56rps
66rps
70rps
40s
90s
60s
40s
40s
240s
82rps
240s
36rps
90s
Notes:
1.
Once the first, 40-second stage of the program is complete, the program proceeds to the subsequent stages in a step-by-step fashion and exits when the
target rotation speed has been reached.
Midea CAC Confidential
Figure 3-3.3: KHA-08(10)RY1 compressor startup program
1
when ambient temperature is above 11°C
Compressor rotation speed (rps)
Figure 3-3.5:
KHA-12(14, 16)RY3
compressor startup program
1
when ambient temperature is above 3°C
38rps
Target rotation speed
Compressor rotation speed (rps)
Time (s)
0
32rps
56rps 66rps
70rps
82rps
40s
60s
40s
40s
120s
120s
42rps
40s
Notes:
1.
Once the first, 40-second stage of the program is complete, the program proceeds to the subsequent stages in a step-by-step fashion and exits when the
target rotation speed has been reached.
M thermal Split
202004
21
Part
3
- Con
trol
Figure 3-3.6:
KHA-12(14, 16)RY3
compressor startup program
1
when ambient temperature is at or below 3°C
38rps
Target rotation speed
Compressor rotation speed (rps)
Time (s)
0
24rps
56rps 66rps
70rps
82rps
40s
90s
40s
40s
240s
240s
42rps
60s
34rps
90s
Notes:
1.
Once the first, 40-second stage of the program is complete, the program proceeds to the subsequent stages in a step-by-step fashion and exits when the
target rotation speed has been reached.
3.3 Startup Control for Heating and Domestic Hot Water Operation
Table 3-3.1: Component control during startup in heating and domestic hot water modes
Component
Wiring diagram
label
6
-16kW
Control functions and states
Inverter compressor
COMP
●
Compressor startup program selected according to
ambient temperature
1
DC fan motor
FAN
●
Fan run at maximum speed
2
Electronic expansion valve
EXV
●
Position (steps) from 0 (fully closed) to 480 (fully open),
controlled according to outdoor ambient temperature,
discharge temperature, suction superheat,
Four-way valve
4-WAY
●
On
Notes:
1. Refer to Part 3, 3.2 “Compressor Startup Program”.
2. Refer to Table 3-4.3 in Part 3, 4.6 “Outdoor Fan Control”.
3.4 Startup Control for Cooling Operation
Table 3-3.2: Component control during startup in cooling mode
Component
Wiring diagram
label
6-16kW
Control functions and states
Inverter compressor
COMP
●
Compressor startup program selected according to
ambient temperature
1
DC fan motor
FAN
●
Fan run at maximum speed
2
Electronic expansion valve
EXV
●
Position (steps) from 0 (fully closed) to 480 (fully open),
controlled according to outdoor ambient temperature,
discharge temperature, suction superheat
Four-way valve
4-WAY
●
Off
Notes:
1.
Refer to Part 3, 3.2 “Compressor Startup Program”.
2.
Refer to Table 3-4.3 in Part 3, 4.6 “Outdoor Fan Control”.
Midea CAC Confidential
Split
Содержание KMK-60RY1
Страница 1: ...SERVICEMANUAL SPLIT TYPE HEAT PUMP R32...
Страница 2: ...Split...
Страница 4: ...M thermal Split 2 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 8: ...M thermal Split 6 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 18: ...M thermal Split Midea M thermal Split Service Manual 16 202004 Midea CAC Confidential Split...
Страница 41: ...M thermal Split 202004 39 Midea CAC Confidential Split...
Страница 42: ...M thermal Split 40 202004 Midea M thermal Split Service Manual Midea CAC Confidential Split...
Страница 113: ...Split...
Страница 114: ...kaisai com...